Should the bus coupler in a 2N data centre switch room be included in a thermography survey?

Yes, with one honest limit. In a 2N switch room the bus coupler is normally open, so its main contacts carry no current and show no heat. The survey should image the busbar and incomer connections on each side under normal load, record the coupler’s position, and image the coupler itself only when planned switching… Read more »