Electrical Thermographic Survey and Inspections UK: Live, No Shutdown

Quick answer: an electrical thermographic inspection uses an infrared camera to find overheating connections, loose terminations and load imbalances in live electrical equipment, before they cause a failure or a fire. Ti Thermal Imaging surveys switchgear, distribution boards, busbars, UPS, PDUs and motor control centres under normal load, with nothing switched off. Our surveys are led by ITC Level 3 thermographers, and every finding is graded with a recommended action.

Plan your electrical thermography survey or call +44 20 3885 7464.

What is an electrical thermographic inspection?

A thermographic inspection images energised electrical infrastructure with an infrared camera. A loose or degraded connection resists current and runs hotter than its neighbours, so it shows up on the thermal image long before it trips a breaker or starts a fire. We survey open switchyards, electrical panels, distribution boards, switches, tap-offs, busbars and other electrical assets.

Why have one carried out?

  • Find faults before they cause downtime: a planned repair in a maintenance window costs far less than an outage.
  • Meet your duty to maintain: the Electricity at Work Regulations 1989 and the Health and Safety at Work Act 1974 expect electrical systems to be maintained in a safe condition. A thermographic report is documented evidence that reasonable steps have been taken.
  • Satisfy insurers: many insurers ask for a thermographic report as part of fire-risk requirements. See what makes an electrical thermography survey insurer-ready.
  • Prioritise spend: graded findings show which assets need attention now and which can wait.

How the survey works

  • Live, no shutdown: thermography only works on energised equipment under load, so everything stays in service.
  • Under load: we survey under normal operating load, ideally 40% or more, so that faults show up. See what load is needed for an electrical thermographic survey.
  • Your safety procedures: we work within your method statements and permit-to-work process. Your appointed electrician opens and closes panel covers, and our thermographer never touches live equipment.

What every report gives you

  • A thermal image and a matching visual photograph of each finding
  • The asset ID and exact location
  • Measured temperatures, with load correction applied where load readings can be taken safely
  • A severity grade and a recommended action with a timescale

Our load-correction method estimates the temperature a component would reach at maximum load, and compares it with the British Standard cable reference temperature of 75 °C to judge severity. We also grade findings using the ANSI/NETA MTS temperature-difference criteria, and work to ISO 18434-1, ASTM E1934 and NFPA 70B, with thermographers certified to ISO 18436-7 / ITC. Reports are produced with our TICOR reporting software and delivered through our online portal, usually the next working day.

How much does an electrical thermography survey cost?

Cost depends on the number and type of assets, site access, how many sites are surveyed, and whether surveys are recurring. See what affects the cost of an electrical thermography survey, read the full guide to electrical thermal imaging surveys, or send us your site details for a quotation.

Specialist and related surveys

What to look for in a survey provider

The market is unregulated, so check before you buy:

  • Thermographers certified to a recognised scheme, ideally Level 2 or Level 3, with electrical competence
  • A calibrated, suitably high-resolution camera, and a stated survey method
  • Reporting that gives you location, temperature, load, severity and a recommended action for every finding, not just a photo
  • Reports you can trend from one survey to the next

Frequently asked questions

Is thermography safe on live electrical equipment?

Yes. It is non-contact, and our thermographers do not touch live equipment. Panel covers are opened by your authorised electrician under your own safety procedures.

How often should electrical systems be surveyed?

Most sites survey critical power infrastructure at least annually, and six-monthly where downtime is costly. Higher-risk or older installations benefit from more frequent surveys.

What happens after a survey finds a hot connection?

Each finding is graded with a recommended action and timescale. Your electrician repairs it, and the next survey confirms the fix.

Do you survey outside the UK?

Yes. As well as UK sites, we carry out electrical thermography across the UAE and the wider Middle East.

Book an electrical thermographic inspection

Call +44 20 3885 7464, email sales@thermalimaging.co.uk or contact us online with your site details and we will propose a survey plan.