Infrared Electrical Inspection UK: Is It the Same as Thermography?

Short answer: for electrical work, infrared inspection, infrared thermography, thermographic survey, thermal imaging survey and electrical thermal imaging all describe the same job. A trained person points an infrared camera at live electrical equipment and looks for connections that are running hotter than they should.

Why so many names for one thing

The camera sees infrared radiation, which is why it gets called infrared. The picture it produces is a thermal image, so the work gets called thermal imaging. The practice of reading those images to assess equipment is thermography, and a planned visit to cover a site is a survey or inspection. Different buyers search with different words, and suppliers use whichever their customers use.

The difference that does matter is not the name. It is who is holding the camera, what load the equipment is under, and what you get in writing afterwards.

What an infrared electrical inspection finds

Most electrical faults that cause heat start at a connection. A terminal that has loosened, a lug that has corroded, a phase carrying more than its share, a fuse holder with a poor contact. As resistance rises the connection heats up, and heat is what the camera shows. Typical items covered include:

  • Switchgear and distribution boards
  • Motor control centres and starters
  • Busbars and bus ducts
  • UPS units, PDUs and battery connections
  • Isolators, contactors and cable terminations

What it does not replace

Infrared inspection is a condition check on live equipment. It does not replace periodic inspection and testing, which checks things a camera cannot see such as earth fault loop impedance and insulation. The two answer different questions, and most commercial sites need both.

What makes the result reliable

Load. The equipment needs to be carrying a representative load. A reading on a lightly loaded circuit can look clean and still hide a poor connection.

Access. The camera needs a clear view of the connection. Covers on, or a connection hidden behind another component, limits what can be assessed. A good report says what could not be inspected.

Interpretation. A warm joint is not automatically a fault. Reading the image against the load, the ambient conditions and similar components nearby is what separates a real finding from a false alarm. Ti surveys are led by ITC Level 3 certified thermographers for that reason.

The report. Each finding should come with a thermal image, a normal photo, the measured temperature, the load at the time and a graded recommended action. At Ti the report is same-day, so you do not wait weeks to learn whether something urgent was found.

Do I need it done live?

Yes. The point of the inspection is to see the equipment working. Ti surveys are carried out live with no shutdown, so production, tenants and critical systems keep running.

Talk to us

If you are comparing quotes, ask each supplier who does the interpretation, what load is needed, and when you get the report. For a survey across the UK, call +44 20 3885 7464.