How to judge a thermal imaging report
A report is the product. The survey is only useful if the person reading it can see what was found, how serious it is and what to do next. Use this checklist on any electrical thermography report, ours or anyone else’s.
The essentials
- Site and equipment identification: each finding is tied to a named board, panel or component.
- Paired images: a thermal image and a visible image of the same item, so the hot spot can be located on site.
- Measured temperature rise: the difference against similar components, not just a maximum temperature.
- Load at the time: the current being carried when the image was taken.
- Emissivity and camera settings: so the reading can be checked.
- Severity rating: graded against a named standard, with a recommended priority.
- Weather and conditions: where they affect the result.
- What was not inspected: and the reason.
- Surveyor details: who carried out and who reviewed the survey, with their certification level.
- Turnaround: a report you can act on while the surveyor’s findings are fresh. Ti issues it the same day as the survey.
Red flags
- Thermal images with no visible image or location.
- A single temperature with no comparison.
- No record of load.
- No severity grading, or grading with no named standard.
- A report that finds nothing on every board, with no limitations listed.
- A wait of days or weeks before you see anything.
Why this matters to insurers and auditors
Insurers and auditors want evidence they can rely on. A report that records the load, the measurement and the grading can be checked. One that does not is hard to defend.
Ask to see one first
If you are comparing suppliers, ask each for an anonymised sample report before you decide. Contact Ti on +44 20 3885 7464 and we will send you one.