Electrical Thermography Survey Checklist for UK Sites

Short answer: an electrical thermography survey runs live, so the one thing that matters is that the equipment is carrying its normal load on the day. Most of this checklist is about making that happen and making sure the thermographer can get to every panel.

Before the survey

1. Confirm the equipment list. Send us the switchgear, distribution boards, motor control centres, UPS, PDUs and any busbar systems you want covered. If you are not sure what is on site, a single-line diagram or a walk-round list is enough to start.

2. Pick a day when the site is running normally. A survey on a quiet bank holiday shows you a quiet bank holiday. Heat from a loose connection rises with current, so a fault that is obvious at full production can be almost invisible at low load. Tell us what normally drives your peak, and we will plan around it.

3. Name a site contact. One person who can sign us in, open doors and tell us if anything has changed on the system recently.

4. Flag anything that cannot be opened. Locked rooms, panels with no access keys, equipment behind racking or stock. Moving things on the day costs survey time.

5. Tell us about recent work. Recently re-terminated connections, new circuits and temporary supplies are all worth a look, and the thermographer will want to know about them.

On the day

The survey is done with the equipment live. Nothing is switched off and you do not need an outage. The thermographer opens panel covers only where it is safe to do so under your permit or site rules, scans each item, and records any hot spot with a thermal image, a normal photo, the measured temperature, the load at the time and where it sits on the board.

Please have someone available who can answer questions about what a given panel feeds. It is the quickest way to rank a finding by what it would take down if it failed.

After the survey

Findings are graded by severity so you can see what needs action now and what can be watched. Ti reports are same-day, which means you know the same day whether anything urgent was found. The full report sits on our online portal, so facilities, maintenance and your insurer can all see the same record.

What not to worry about

You do not need to clean the equipment, de-energise it or have the covers off before we arrive. You do not need to supply a ladder or special access beyond what the room normally has. If there is a restriction we should know about, tell us when booking and we will plan for it.

Who carries out the survey

Surveys are led by ITC Level 3 certified thermographers. That matters on the day, because deciding whether a warm connection is a fault or normal loading is a judgement call, and it is made on site by the person who will sign the report.