What should an electrical thermography survey cover at a spray drying plant?

It should follow the power from the LV switchboards through the whole drying line: feed and evaporator pumps, MVR and vacuum fans, the atomiser drive, inlet and exhaust air fans, air heater controls, fluid bed and cyclone fans, pneumatic conveying, powder silos and the packing hall. It is all imaged live while the dryer is running, comparing like with like so process heat is not mistaken for a fault.

Survey while the dryer is running

Spray dryers making milk powder, whey, starch, coffee or other food ingredients usually run continuously for long production runs between cleans. That is when the fans, pumps and atomiser carry their working current, and thermography only shows a weak connection while current is flowing through it. On a dairy site the busiest period is often the spring milk peak, when the dryers run hardest. The survey is booked during normal production, not a wash-down or shutdown, and the report records what was running when each panel was imaged.

What the scope should include

  • LV distribution: main LV switchboards and outgoing feeders to the evaporator, dryer tower, packing hall, CIP and site services.
  • Evaporator: feed and product pump starters, MVR or thermal vapour fan drives, vacuum pumps and condenser water pumps.
  • Dryer tower: high-pressure feed pump drives, the atomiser drive panel, and the inlet and exhaust air fan VSDs, often the largest drives on site (see MCCs and VSDs imaged while running).
  • Air heating: burner or steam heater control panels and any electric air heater supplies.
  • After the tower: fluid bed dryer and cooler fans, cyclone and bag filter fans, rotary valves and sieves.
  • Powder handling and packing: pneumatic conveying blowers, silo panels, blending, and the bagging, big-bag and canning lines.
  • Utilities: CIP sets, boiler house auxiliaries, refrigeration and the compressed air plant.

The survey covers electrical panels and connections. Dust explosion assessments, explosion vent and suppression checks, burner servicing and mechanical inspections are separate jobs and sit outside this scope.

Traps a good thermographer avoids

  • Process heat. The drying chamber, hot air ducts, evaporator and steam pipework are hot by design, and panels near them can read warm all over. That is not a finding. What matters is the difference in °C between matching connections, phase to phase, on the same circuit.
  • Changing load. Fan and pump speeds change with product, solids and air temperature, so the thermographer records the running state of each drive and compares like with like.
  • Reflections. Stainless steel ducting, bare copper and polished cabinets reflect heat, so the thermographer changes angle to confirm a hot spot belongs to the connection.
  • Powder on enclosures. Fine powder settles on panels and changes how surfaces read, so readings are taken from the connections themselves with the panel open.
  • Anti-condensation heaters. Panel heaters warm the enclosure, not the connection, and are not reported as findings.

Working on a food site

The thermographer follows the site induction, hygiene and PPE rules, including any dust zone and high-care controls, and keeps to agreed routes around the tower and packing hall. Panels are opened by the site’s electrician under the site’s own permit system (see who opens the panels). Production carries on as normal.

What the report gives you

A same-day report that locates each finding by panel, circuit and phase, with a thermal and visual image pair, the measured temperature, where it was taken, the difference in °C from the matching reference and the running state at the time. Areas that could not be imaged safely are listed. Ti inspects and reports. The site’s electrical team or contractor investigates any finding with the equipment isolated.

Why load matters

Load is what makes a weak connection show. On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. On a spray drying plant that means surveying mid-run, with the fans, pumps and atomiser working.

Frequently asked questions

Does the dryer have to stop for the survey?

No. Thermography images energised equipment on load, so the survey is done while the dryer is producing. A wash-down or shutdown is the worst time because the main drives are not running.

How often should a spray drying plant be surveyed?

Most sites survey once a year during production, and again after major changes such as a new fan drive, atomiser, evaporator or switchboard.

Can the findings feed into the next planned shutdown?

Yes. A survey mid-run gives the engineering team a list of findings by panel and circuit to investigate when the line is isolated at the next planned stop.