Should an office server room or comms room be included in an electrical thermography survey?

Short answer: yes. An office server or comms room often has its own small UPS, a dedicated distribution board, rack PDUs and a split cooling unit, all running around the clock and rarely looked at. They can be imaged live as part of the building’s annual survey, with nothing switched off, and usually add little time to the visit.

Why these rooms get missed

Building surveys tend to follow the landlord’s switch rooms, risers and plant. The server room sits on a tenant floor, behind its own access control, and is looked after by IT rather than facilities. It may have been fitted out years ago and extended rack by rack since. Yet it is often the one room in an office where a failed connection stops the whole business: phones, network, door access and on-site servers.

What is surveyed

  • The supply into the room: the sub-main and the dedicated distribution board, including any boards added as racks were added.
  • The UPS: input and output connections and its bypass switch, imaged with covers removed where the UPS allows it safely.
  • Rack PDUs and plug connections: including extension leads or daisy-chained strips added over time.
  • Cooling: the isolator and supply to the split or close-control unit, which is often the first thing to fail in summer.
  • Comms cabinets on other floors: small floor cabinets with a PoE switch and a local supply, where included in the scope.

How it is done without disrupting IT

The survey is booked with the IT team as well as facilities, so access and timing suit both. Panels are opened by the site’s electrician or authorised person; rack doors are opened by IT. Everything stays live. A working weekday is usually better than a weekend, because the room is carrying its normal load. Readings are taken where the surface gives a true reading, compared like for like with a matching phase or connection, and logged with the load at the time. UPS units and power supplies run warm by design, so findings are given as measured temperatures and the difference in °C, not as a single hot spot on an image. Ti reports what was measured; your electrical contractor or UPS supplier decides what to do.

What you get

The server room appears in the same report as the rest of the building, with a thermal and visual image for every finding, its location by room, rack and board, and a list of anything that could not be opened. Reports are delivered the same day. Surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company that also surveys large data centres from commissioning to live operation.

Frequently asked questions

Do the servers need to be shut down?

No. The survey images live equipment under its normal load; nothing is switched off.

Who should arrange it, the landlord or the tenant?

Usually the tenant, as the room is part of its own installation. It can be added to the landlord’s visit if both agree.

How often should a server room be surveyed?

Once a year as a minimum, and after any significant change such as a new UPS or more racks. Your insurer may set its own interval.