Data centre thermography surveys for live systems, from commissioning to live operation
Ti Thermal Imaging carries out electrical thermography for data centres at every stage: commissioning and load bank testing, handover, and planned surveys of live halls. Our ITC Level 3 thermographers image switchgear, busbar trunking and tap-off units, UPS, PDUs, ATS and generator panels under load, with nothing switched off. Ti is a Level 3 certified company, and reports are produced on site.
At commissioning on a London data centre build, our thermography found 16 busbar sections over 80 °C under test load, the highest 103.5 °C at a tap-off unit, all located and recorded before handover. See when busbars should be imaged at commissioning.
In a live data centre, an overheating connection is a threat to uptime. Thermography finds it while everything stays in service, including at sites managed by global FM providers.
Our thermal imaging work has featured on BBC News and ITV.
Plan your data centre survey or call +44 20 3885 7464.
Why data centres need electrical thermography
Data centre power chains run continuously and often close to their design load. Loose terminations, degraded connections and unbalanced loads produce heat long before they cause a trip or a fire. Thermography finds them early, so you can plan repairs into a maintenance window instead of reacting to an outage. See the 7 electrical failure risks that cause data centre downtime.
What we survey
- HV and LV switchgear and main distribution boards: see switchgear thermography for data centres
- Busbar trunking, bus risers and tap-off units: see busbar thermography inspections
- UPS systems, static switches and battery connections
- Power distribution units (PDUs) and remote power panels
- Automatic transfer switches (ATS) and generator connections
- Cooling plant: CRAC/CRAH units, chillers, pumps and motors
Surveying live with zero downtime
Thermography only works on energised equipment under load, so it fits naturally into a live data centre:
- No shutdown: equipment stays in service throughout the survey.
- Under load: we survey under normal operating load, ideally 40% or more, so faults show up.
- Your permit to work: we work within your method statements, change control and permit-to-work process. Your appointed electrician opens and closes panel covers, and our thermographer never touches live equipment.
- Planned around your operations: surveys can be phased by hall, power chain (A and B) or out of hours to match your maintenance windows.
Reports your engineers and insurers can act on
Every finding is documented with:
- A thermal image and a matching visual photograph
- The asset ID and exact location, such as hall, room, panel and circuit
- Measured temperatures and load readings where it is safe to take them, with load correction applied
- A severity grade and a recommended action with a timescale
We grade electrical anomalies using the ANSI/NETA MTS temperature-difference criteria:
| ΔT between similar components | ΔT over ambient | Recommended action |
| 1–3 °C | 1–10 °C | Investigate |
| 4–15 °C | 11–20 °C | Repair as time permits |
| — | 21–40 °C | Repair as soon as possible |
| >15 °C | >40 °C | Repair immediately |
We work to ISO 18434-1, ASTM E1934 and NFPA 70B, with thermographers certified to ISO 18436-7 / ITC. Read more about why thermography matters in data centre busbar testing.
Planned thermography programmes and annual PPM
A single survey shows you today’s condition. A planned programme shows you the trend. We set up recurring surveys, typically every six or twelve months depending on how critical the site is, that:
- Use a consistent asset register, so findings can be compared between surveys
- Track whether previous findings have been fixed
- Show which assets are deteriorating, to support capital planning
- Provide documented evidence for insurers, auditors and clients’ SLA reporting
Find out more about data centre electrical thermography for annual PPM.
Experience
- Planned electrical thermography programmes at commercial and data centre sites for global FM providers
- More than 700 electrical thermography inspections across a national distribution and logistics network since 2018
- Electrical thermography across the UAE and wider Middle East
- Data centre thermography across Europe: see European data centre thermography
What our clients say
“Richard and the team have been amazing to work with during testing and commissioning on a data centre. Producing quality reports with the brilliant software they are using quickly and efficiently. The TICOR software enables them to deliver my reports within a few minutes of completing the inspections which is incredibly efficient.”
David Graham, data centre testing and commissioning. 5-star Google review
“We have been working with Ti Thermal Imaging team for approx. 10 years. They are very professional and always provide a first class service.”
Darren Helliwell. 5-star Google review
“We’ve used Ti Thermal Imaging for multiple electrical thermographic inspections across our portfolio. Always professional, responsive, and easy to work with. Highly recommend.”
Richard Clarke. 5-star Google review
See also: when to thermally image busbars during data centre commissioning.
Frequently asked questions
Is thermography safe in a live data centre?
Yes. It is non-contact, and our thermographers do not touch live equipment. Panel covers are opened by your authorised electrician under your own safety procedures.
How often should data centre electrical systems be surveyed?
Most data centres survey critical power infrastructure every six months, and at least annually. Higher-risk or older installations benefit from more frequent surveys.
Can you survey enclosed switchgear?
Where covers cannot be removed safely, infrared inspection windows can be installed so future surveys can be done without opening the panels. We can advise on where windows would help most.