What an electrical thermography survey looks at
A loose lug, an overloaded busbar joint or a worn contactor runs hotter than its neighbours long before it fails. Thermography lets a Level 3 thermographer see that heat while the equipment is live, so the fault can be planned out instead of arriving as an outage.
A survey covers the incoming supply, main and sub-distribution boards, motor control centres, switchgear, isolators, busbars and cable terminations. Panel covers are opened by a competent person on site so the connections can be seen directly. Anything that cannot be safely opened is recorded as not inspected, so the report never implies more than was seen.
Why the load matters
A fault only heats up when current flows through it. A survey done with the building lightly loaded can miss a connection that would glow under normal demand. The thermographer records the load at the time of the scan, and where the load is low the report says so.
How faults are graded
Findings are graded by the temperature rise against similar components under similar load, using the ANSI/NETA MTS severity bands. Each finding has a visible image, a thermal image, the measured temperature difference and a priority, so the person who has to fix it knows what to do first.
Your report the same day
You do not wait days for the results. The graded report is issued the same day as the survey, so any hot connection can be dealt with straight away instead of sitting in a queue.
What you get back
- A thermal and visible image for every finding
- Measured temperature rise, load at the time and emissivity assumptions
- A severity rating and recommended priority for each fault
- A clear list of anything not inspected and why
Ti inspects and reports. We do not carry out repairs, so the report is independent of whoever fixes the fault.
Common questions
Does the supply need to be switched off? No. The survey is carried out live, which is why it causes no downtime.
How quickly do I get the report? The same day as the survey.
How often should it be done? Many sites survey annually. Insurers, critical sites and heavily loaded equipment often justify a shorter interval.
Does it replace fixed wire testing? No. The two find different things. See our guide on thermography and fixed wire testing.
To discuss a survey, call Ti on +44 20 3885 7464 or send us your site details for a quote.