Thermography vs Fixed Wire Testing: Why Commercial Sites Need Both

Two different tests

Fixed wire testing, usually reported as an EICR, and thermography are often confused. Both look at your electrical installation, but they answer different questions.

Fixed wire testing

Fixed wire testing checks the installation against BS 7671. It is a dead test: circuits are isolated and measurements such as insulation resistance and earth fault loop impedance are taken. It tells you whether the installation is safe and compliant at that moment.

Thermography

Thermography is a live survey. It looks for heat in connections, joints and components while they carry real current. It finds the developing faults, such as loose terminations, overloaded conductors and failing components, that can look perfectly fine on a dead test.

What each can miss

  • A dead test cannot see a connection that only overheats under load.
  • Thermography does not measure insulation resistance or earth fault loop impedance, so it does not show compliance with BS 7671.

Side by side

Fixed wire testingThermography
SupplyIsolatedLive, under load
DowntimeOften requiredNone
FindsCompliance and insulation faultsHot connections and developing failures
StandardBS 7671Severity graded, for example ANSI/NETA MTS
Ti reportNot applicableIssued the same day as the survey

Using both

Many sites plan thermography ahead of an isolation or shutdown so that any hot connections found can be dealt with in the same window. Because our graded report comes back the same day, there is no waiting for results before the work is planned. It also gives insurers a second independent view of electrical risk.