Short answer: ask four things. Is the power path feeding your space surveyed with thermography, from switchgear and UPS to the floor PDUs or busbar serving your cage? How often, and under what load? Who carries it out and at what level? And will you see a summary of findings that affect your supply? Good operators answer all four without hesitation.
Why it matters to the customer, not just the operator
In a colocation data centre you own the racks, but almost everything upstream belongs to the operator: the intake, LV switchboards, UPS, static switches, floor PDUs or overhead busbar and the tap-offs feeding your cabinets. A loose or overheating connection anywhere on that path can take out one of your feeds. Electrical thermography is one of the few checks that looks at those connections while they are live and loaded, so it is a fair question to ask when you sign, renew or expand.
The questions worth asking
- What is in scope? The whole power path to your space, or just the main switch room? Ask specifically about the PDUs, remote power panels or busbar tap-offs that serve your racks.
- How often? Once a year as a minimum on live sites is common, with a survey after major works, a new hall going live or a big load increase. Your contract or your own insurer may set its own expectation.
- Under what load? A survey only shows problems on circuits carrying meaningful current. Ask whether load is recorded with each reading, and how dual-fed (2N) supplies are handled when each side carries only part of the load.
- Who does it, and at what level? Independent thermographer or the maintenance contractor, and what certification they hold. ITC Level 3 means the person can set the method and stand behind the findings.
- What will you see? Operators decide what they share. A reasonable ask is confirmation that the survey was done, and a short summary of any finding on equipment feeding your space, with its status.
What a good answer looks like
A clear date for the last survey and the next one, a scope that reaches your floor PDUs or busbar, load recorded with each finding, and a named process for closing findings out and re-imaging them under load. Findings on customer-owned rack PDUs and cabling should come back to you through the operator’s normal customer channel, so they are not lost.
What commissioning can show
The earliest point to catch a problem is before the hall goes live. On one London data centre build, commissioning thermography found 16 busbar sections above 80°C under test load, the highest 103.5°C at a tap-off. Each was reported with its location and images before handover. If you are moving into a new hall, it is worth asking whether commissioning thermography was done and whether its report is the baseline for later surveys.
How Ti works with operators
Ti carries out live surveys for operators, so customer equipment stays powered and nothing is switched off. Panels are opened by the site’s own authorised staff, readings are given as measured temperatures with the difference in °C and the load at the time, and the report is delivered the same day. Ti inspects and reports only. Surveys are led by ITC Level 3 thermographers, and Ti is a Level 3 certified company.
Frequently asked questions
Can a colocation customer arrange its own thermography survey?
Usually only of its own equipment, and only with the operator’s agreement and escort. Upstream equipment is the operator’s to survey.
Will the operator share the full report?
That is the operator’s decision. Many will share a summary of findings that affect a customer’s supply.
Should rack PDUs be included?
Yes, where the customer agrees. Rack PDUs and their plug connections can be imaged without switching anything off.
Related reading
- Who arranges access for a survey in a colocation data centre?
- How often should a live data centre be surveyed, and by whom?
- Rack PDUs in a live data hall
- Is there enough load on a dual-fed 2N site?
- Data centre electrical thermography
- Busbar thermography at commissioning
- Switchgear thermography
- Annual PPM thermography
- 7 electrical risks behind downtime
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.