Ti Thermal Imaging carries out electrical thermography for data centres across Europe. Our ITC Level 3 thermographers travel from the UK to survey switchgear, busbar trunking, UPS, PDUs, ATS and generator connections under load, with nothing switched off. Your report is ready the same day. We work at commissioning, in live halls and on planned annual programmes.
Ti is a Level 3 certified company. We inspect and report. We do not carry out repairs, so our findings go to your own electrical contractor with the image, the location and the recommended action already written up.
Plan a European data centre survey or call +44 20 3885 7464.
Three jobs we do for data centres in Europe
- Commissioning. Imaging busbars, switchgear and UPS while the load bank is running, so loose connections are found and fixed before handover. See commissioning thermography in Europe.
- Live halls. Surveying energised equipment under normal load, hall by hall or by A and B power chain, inside your permit-to-work and change control.
- Planned programmes. Six or twelve monthly surveys on one asset register, so each report shows what was fixed, what is getting worse and what to budget for. See annual PPM thermography.
Where we survey
The big five markets (Frankfurt, London, Amsterdam, Paris and Dublin) are where most European capacity sits, and where grid limits mean existing halls are run hard. Newer capacity is also going into the Nordics, Iberia, Italy and Poland. We will travel to any of them.
- Data centre thermography in Ireland (Dublin and beyond)
- Data centre thermography in the Netherlands (Amsterdam and Schiphol)
- Data centre thermography in Germany (Frankfurt and Hesse)
- Data centre thermography in France (Paris and Marseille)
- UK sites: see data centre electrical thermography in the UK
Elsewhere in Europe, tell us the site and the dates and we will say what is practical.
What we survey
- HV and LV switchgear and main distribution boards, see switchgear thermography for data centres
- Busbar trunking, risers and tap-off units
- UPS systems, static switches and battery connections
- PDUs and remote power panels
- Automatic transfer switches and generator connections
- Cooling plant: CRAH units, chillers, pumps and motors
How a cross-border survey works
- Scope. You tell us the halls, the power chains, the load and your maintenance windows. We agree what is surveyed and in what order.
- Site rules. We work inside your method statements, induction and permit to work. Your electrician opens and closes panel covers. Our thermographer never touches live equipment.
- Survey under load. Heat from a poor connection rises with the square of the current, so we survey at the highest stable load the site can give us.
- Same-day report. Every finding has a thermal image, a matching photo, the asset and location, the measured temperature, the load at the time, a severity grade and a recommended action.
- Re-check. After your contractor repairs the findings, we can image them again so the record shows they were closed out.
Experience
- At commissioning on a London data centre build, our thermography found 16 busbar sections over 80 °C under test load, the highest 103.5 °C at a tap-off unit, all located before handover.
- More than 700 electrical thermography inspections across a national distribution and logistics network since 2018.
- Planned electrical thermography programmes at commercial and data centre sites for global FM providers.
- Electrical thermography across the UAE and the wider Middle East.
Between surveys
A survey is a snapshot. For critical power chains, fixed thermal sensors give early warning between surveys. See AI continuous thermal monitoring for data centres.
Frequently asked questions
Who carries out data centre thermography across Europe?
Ti Thermal Imaging, a Level 3 certified thermography company based in the UK. Our ITC Level 3 thermographers travel to data centres in Ireland, the Netherlands, Germany, France and elsewhere in Europe.
What is data centre electrical thermography?
It is an inspection with a thermal camera of energised electrical equipment under load. It shows overheating connections in switchgear, busbar, UPS, PDUs and generator panels before they cause a trip, an outage or a fire.
Does a data centre need to shut anything down for a thermography survey?
No. Thermography only works on energised equipment under load, so nothing is switched off. Your electrician opens panel covers under your permit to work, and our thermographer never touches live equipment.
What load does the equipment need to be under?
The higher the better. Heat from a poor connection rises with the square of the current, so a fault that is barely visible at 20% load can be serious at full load. On live sites we aim for 40% load or more, and we record the load at the time of every image.
When should thermography be done at commissioning?
During load bank or integrated systems testing, when current is flowing through the power chain. That is when loose busbar joints and switchgear terminations show up, while your contractor can still fix them before handover.
How often should data centre electrical systems be surveyed?
Most operators survey critical power equipment every six months, and at least annually. Older or heavily loaded installations benefit from more frequent surveys.
What does a thermography report contain?
For every finding: a thermal image and a matching photo, the asset and exact location, the measured temperature, the load at the time, a severity grade and a recommended action. We grade to ANSI/NETA MTS temperature-difference criteria. You receive the report the same day.
Does thermography replace electrical testing?
No. It is a condition-monitoring tool that finds faults producing heat at the load present on the day. It complements periodic electrical testing and does not replace it.
Do you repair the faults you find?
No. We inspect and report. Your own electrical contractor carries out repairs, and we can image the repaired connections again so the record shows each finding closed.
What language is the report in?
English.
What affects the cost of a European data centre survey?
The number of assets and halls, access and permit arrangements, the load available, report depth and travel. Send us the site details and your maintenance window and we will propose a plan.
Plan your European data centre thermography
Tell us about your site, your power chain and your maintenance windows, and we will propose a survey plan. Call +44 20 3885 7464, email sales@thermalimaging.co.uk or contact us online.