What should an electrical thermography survey cover at a flour mill or grain store?

Short answer: a flour mill or grain store survey should cover the incoming supply and main switchboard, the MCCs and drive panels for roller mills, elevators, conveyors, fans and blowers, and the dryer and aeration panels. Panels inside dust-hazard zones are agreed with the site beforehand. Image during a full milling run or intake, when drives carry working current.

Why mills and grain stores need a planned survey

A mill runs a long chain of motors: intake conveyors and elevators, cleaning and conditioning, roller mills, sifters, pneumatic conveying fans and blowers, then packing and bulk loading. Most of them sit on a handful of motor control centres, and many sites run around the clock. An unplanned stop holds up the whole line.

Thermography checks the connections feeding that equipment under real load, with no shutdown, so anything that stands out can be planned into the next maintenance stop.

What to include

  • Incoming supply, main LV switchboard and sub-boards for the mill, warehouse and offices
  • MCCs and starters for roller mills, sifters, elevators and conveyors
  • Drive panels and inverters for fans, blowers and pneumatic conveying
  • Grain dryer and aeration fan panels, including outdoor kiosks at the store
  • Packing, palletising and bulk loading panels
  • Support plant: compressors, dust extraction and filter panels

Dust-hazard zones

Mills and grain stores have areas classified for combustible dust under the site’s own DSEAR assessment. Most MCCs and switchrooms sit outside those zones. Anything inside a zone is only opened and imaged if the site’s assessment and permit allow it; otherwise it is listed on the report as not imaged, so nobody assumes it was checked.

Timing: full run or harvest intake

A mill is best imaged part-way through a normal milling run, with the main drives at working load. A grain store is different: dryers, intake conveyors and aeration fans work hardest during harvest intake, and some barely run outside it. We agree the route with the site so each panel is imaged while its equipment is running, and the load is recorded with every image so next year’s survey compares like with like.

Heat traps a thermographer has to rule out

  • Dust layers: a film of flour or grain dust on a cover or component changes what the camera sees, so readings are taken on the connection itself with the cover open where it is safe to do so.
  • Warm by design: motors, gearboxes and dryer casings run warm in normal service. Readings are taken at the electrical connection, not the machine body.
  • Sun on outdoor kiosks: dryer and aeration panels outdoors can be heated by direct sun, so they are imaged with that in mind and compared with matching panels.

What the report gives you

Each finding comes with its location by panel and circuit, a thermal image with a matching photo, the measured temperature, the load at the time and the difference in °C from a matching phase or identical unit. Ti inspects and reports; your maintenance team carries out any work. Reports are on our online portal, usually the same or next working day.

Frequently asked questions

Does the mill need to stop?

No. Thermography needs the equipment running. Covers are opened one at a time by your authorised electrician while production carries on.

How often should a mill be surveyed?

Once a year is a common minimum. Mills running around the clock, or with older MCCs, often survey every six months.

Can a grain store be surveyed outside harvest?

The boards can, but dryers and intake equipment may be idle. Image those panels during intake, when they carry working current.

Related reading

Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.

Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details

About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.