Short answer: run it as one programme, not separate site jobs: one written method, one thermographer standard (Level 2 or above, with a Level 3 overseeing), the same asset naming and report format at every site, load recorded with every image, and each site surveyed at a fixed point in its own change calendar. Then findings compare across the estate.
Why buying site by site leaves gaps
Many operators grow one site at a time, and the thermography grows the same way. One site uses the main contractor’s thermographer, another a local firm, a third was surveyed at commissioning and not since. Each report names the equipment differently, records load differently (or not at all) and uses its own criteria for what gets flagged.
The result is a set of reports that cannot be compared. A connection flagged at one site may not be mentioned at another, and nobody at estate level can say which sites carry the most open findings.
What to standardise once
- Method and RAMS: one method statement agreed with your EHS team, then adapted for each site’s access, permit and change process.
- Scope by asset class: LV side of intake switchgear and transformers, main LV switchboards, UPS input and output, static transfer switches, busbar and tap-offs, floor PDUs and RPPs, generator and ATS panels, and the mechanical plant panels.
- Asset naming: site, hall, room and asset ID taken from your own CMMS, so a finding drops straight into the work order system.
- Report format: thermal image with a matching photo, measured temperature, where it was taken, load at the time, and the difference in °C from a matching phase or identical unit.
- Criteria for prioritising findings: agreed up front and applied the same way at every site.
Scheduling each site at the right time
Every site has its own change freezes, maintenance windows and customer moves. Survey each one at a fixed point in its own calendar, at normal operating load and outside any window where load has been transferred. Keeping the same point each year means the next survey compares like with like, site by site.
New halls are the exception. A new hall gets its own commissioning survey under load bank, then joins the annual cycle.
Start every new site with a baseline
Commissioning is where each site’s record should begin. On one London data centre build, Ti’s commissioning thermography found 16 busbar sections over 80°C under test load, the highest reading 103.5°C at a tap-off. Those were found and reported while the hall was still under test, not once customers were live. The same applies to a site bought or taken over: a baseline survey at handover gives a dated starting point.
What the estate gets back
Each site gets its own full report. On top of that, an estate summary shows open findings by site, repeat findings at the same asset, and findings closed since the last survey. That is the view an operations director, an insurer or a customer audit usually asks for. Ti inspects and reports; your maintenance contractor carries out any work, and the next survey confirms it.
Frequently asked questions
Can one supplier cover sites across the UK?
Yes. Ti’s thermographers travel to sites across the UK, and Ti also has a separate company in the UAE.
Should every site be surveyed at the same time of year?
Not necessarily. What matters is a fixed point in each site’s own calendar, at normal load, so each site compares with its own last survey.
Does an estate programme replace commissioning surveys?
No. Each new hall still needs its own survey under load bank before it goes live; it then joins the estate’s annual cycle.
Related reading
- Data centre electrical thermography
- Busbar thermography at commissioning
- Switchgear thermography
- How we plan annual PPM thermography
- 7 electrical risks behind downtime
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.