Yes. Shore power pillars, pontoon feeder boards and the marina’s main switchboard can all be surveyed live with a thermal camera, with nothing switched off. The timing matters most: a pillar only shows a problem while boats are plugged in and drawing current, so survey when berths are full and boats are using power, and record the load at every reading.