Short answer: yes, where the temporary supply carries live IT or critical load. Temporary generators, temporary distribution boards and the plug-in connectors and cable joints that tie them into the site are installed quickly, often moved, and carry real load for the length of the works. A live thermographic survey at that load shows any connection running hotter than its matching neighbours while there is still time to act on it.
When a data centre runs on temporary power
Temporary power turns up on most data centre programmes at some point: a UPS or switchgear replacement, a generator overhaul, an LV board change, or a new hall being built while the rest of the site stays live. For days or weeks, part of the critical load is carried by equipment that was not there last month and will not be there next month.
That equipment usually sits outside the planned PPM thermography scope, because it is not on the asset register. It is also the part of the power path with the most connections made in a hurry, under a works programme, by people who will leave site when the job ends.
What is surveyed
- Plug-in connectors: single-core connectors and their mating halves along each temporary cable run.
- Temporary distribution boards: incoming and outgoing terminals, where the cover can be opened safely.
- The connection into the site: the point where the temporary supply lands on the site’s switchgear, connection box or changeover panel.
- Generator output terminals: where the hire company’s engineer can open the enclosure safely with the set running.
- Cable joints and lugs in view on each run.
Panels are opened by the site’s authorised person or the hire company’s engineer, under the site’s permit. The thermographer images; nobody else touches the connections.
When to survey
Once the temporary supply has taken its working load, early in the works window. That gives the people who installed it time to look at anything the survey raises while they are still on site. If connectors are moved or re-made part way through the works, the moved runs are surveyed again.
Load matters. A temporary set idling on no load tells you very little, so the survey is planned for the period when it is carrying the load it was brought in for, and the load is recorded with each image. If that load sits overnight or at the weekend, the survey goes then.
Reading the images honestly
A running generator gives off a lot of heat of its own from the engine and exhaust, and outdoor cable runs pick up sun. Neither is a fault. Readings are taken on the connection itself, compared like for like with a matching connector on a similar load, and given as the measured temperature and the difference in °C, with the location. Ti reports what was measured and where. The hire company or works contractor decides what to do about it.
Why it is worth the visit
Connections made under test and under time pressure are where commissioning thermography earns its keep. On one London data centre build, Ti’s commissioning thermography found 16 busbar sections over 80°C under test load, the highest reading 103.5°C at a tap-off. Temporary power is made under the same kind of pressure, and it carries critical load from day one.
Frequently asked questions
Is this the same as surveying the site’s own generators?
No. The permanent generators and ATS panels are part of the annual survey. This covers the temporary kit brought in for the works.
Does anything need to be switched off?
No. The survey is done live, with the temporary supply carrying its normal works load.
Who receives the report?
Usually the site’s operations team, with a copy for the works contractor or hire company so they can act on any finding before demobilising.
Related reading
- Data centre electrical thermography
- Can generator and ATS changeover panels be imaged live?
- Survey after a UPS or switchgear replacement
- Busbar thermography at commissioning
- Switchgear thermography
- How we plan annual PPM thermography
- 7 electrical risks behind downtime
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.