Short answer: at a chipboard, MDF or OSB panel board plant, survey the incoming supply and main switchboards, the MCCs and drives for chippers, flakers and refiners, the dryer and energy plant panels, resin dosing, the forming line and continuous press hydraulics, sanding and cut-to-size lines, dust extraction and spark detection panels. Image at steady production, not during start-up or a product change.
Why a panel board plant needs a planned survey
A panel board line is one long chain: dry, blend, form, press, cool, sand, cut. If one large motor or feeder board trips, the whole line stops, and most of these plants run around the clock.
Thermography checks the connections feeding that chain under real working load, with nothing switched off. Anything that stands out goes in the report with its location and measured temperature, so the site can plan any work into the next maintenance stop instead of losing production to a breakdown.
What to include
- Incoming supply, main LV switchboards and sub-boards for the line, energy plant, yard and offices
- Wood preparation: debarker, chipper, flaker and screen MCCs and starters, and the LV supplies for MDF refiners
- Dryers and energy plant: dryer fan drives, burner and thermal oil heater control panels, and the boards that feed them
- Resin and additives: dosing pump panels and blender drives
- Forming and pressing: forming station drives, press hydraulic power pack starters, press control panels and the cooling turner
- Finishing: sanding line drives, cut-to-size saws, stackers, and any laminating or short-cycle press lines
- Safety and handling: spark detection and extinguishing panels, dust extraction fan starters, conveyors, wrapping and forklift charging
Large refiners and main fans are sometimes fed at high voltage. The scope of works should say exactly which switchgear is included, so the report and the site agree on what was covered.
Dust-hazard zones
Wood dust and fibre are combustible, and parts of a panel plant will be classified under the site’s own DSEAR assessment, usually around dryers, cyclones, filters, silos and sanding extraction. Most MCCs and switchrooms sit outside those zones. Anything inside a zone is only opened and imaged if the site’s assessment and permit allow it; otherwise it is listed on the report as not imaged, so nobody assumes it was checked.
Timing: steady production
Refiners, dryer fans and press hydraulics draw their normal working current once the line is settled. During start-up, a thickness change or a slow run after a stop, the load is lower and some panels will show far less. We agree the route with the production manager so each panel is imaged while its part of the line is running normally, and the load is recorded with every image so next year’s survey compares like with like.
Heat traps a thermographer has to rule out
- Heat by design: press platens, thermal oil pipework, dryer casings and hot board leaving the press are all hot in normal service. Readings are taken at the electrical connection, not near process heat, and panels close to the press are checked for heat carried in from outside the enclosure.
- Dust on covers and components: a layer of fibre or sanding dust changes what the camera sees, so readings are taken on the connection itself with the cover open where it is safe to do so.
- Bare metal and reflections: shiny busbars, enclosure walls and steel press frames reflect heat from nearby sources, so a suspect reading is checked from a second angle before it is reported.
Why load matters
A connection that looks normal at light load can show up clearly at full load. On a London data centre build, our commissioning thermography recorded 16 busbar sections above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Those readings were taken because the system was carrying load when it was imaged.
What the report gives you
Each finding comes with its location by panel and circuit, a thermal image with a matching photo, the measured temperature, the load at the time and the difference in °C from a matching phase or identical unit. Ti inspects and reports; your maintenance team or electrical contractor carries out any work. Reports are on our online portal, usually the same or next working day, in a format insurers and auditors recognise.
Who should do it
Look for a thermographer certified to at least Level 2, with Level 3 oversight, who works within your permit-to-work. Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Your authorised electrician opens and closes panel covers; our thermographer does not touch live equipment.
Frequently asked questions
Does the line need to stop?
No. Thermography needs the equipment running. Covers are opened one at a time by your authorised electrician while the line keeps producing.
How often should a panel board plant be surveyed?
Once a year is a common minimum. Plants running continuously, or with older MCCs, often survey every six months or a few weeks before a planned shutdown.
Can the dryer and energy plant be surveyed while they run?
Yes. Fan drives, burner and thermal oil heater control panels are imaged at working load. Anything inside a classified zone is only opened if the site’s DSEAR assessment and permit allow it.
Related reading
- How we plan annual PPM thermography
- Switchgear thermography
- 7 electrical risks behind downtime
- Busbar thermography at commissioning
- Data centre electrical thermography
- Should a factory have its survey before or during its planned shutdown?
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.