What should an electrical thermography survey cover at a textile or carpet mill?

Short answer: at a textile or carpet mill, survey the incoming supply and main switchboards, the MCCs and drives for opening, carding and spinning, the looms or tufting machines, the dye house pumps and controls, the stenter and backing oven panels, and the compressors and humidification plant. Image during normal production, after lint is cleared from the panels you can safely open.

Why a textile mill needs a planned survey

A textile or carpet mill runs long lines of motors and drives: fibre preparation, spinning, weaving or tufting, dyeing, drying and finishing. Many mills run around the clock, and a tripped drive board stops a whole section.

Thermography checks the connections feeding those lines under real working load, with nothing switched off. Anything that stands out goes in the report with its location and measured temperature, so the site can plan any work into the next stop instead of losing a shift to a breakdown.

What to include

  • Incoming supply, main LV switchboards and sub-boards for each production hall, warehouse and offices
  • Fibre preparation and spinning: bale opener, blending, carding and drawing MCCs, spinning and twisting frame drives
  • Weaving and tufting: loom and tufting machine supplies, creel and beam drives
  • Dye house: dye vessel pump and agitator panels, dosing, effluent pumps and boiler house control panels
  • Drying and finishing: stenter and backing line drive panels, burner and fan control panels, shearing and cropping machines, cutting and roll-up lines
  • Services: air compressors, humidification and air-handling plant, fibre extraction fans, conveyors and forklift charging

Lint, fibre and fire risk

Fibre and lint settle on and inside panels, and textile mills take fire risk seriously. Readings are taken on the connection itself with the cover open where it is safe to do so, because a layer of fluff changes what the camera sees. If the site’s own fire or DSEAR assessment restricts opening panels in an area, those panels are listed on the report as not imaged, so nobody assumes they were checked.

Timing: normal production

Spinning frames, looms, dye pumps and stenter fans draw their normal working current once a run is settled. During start-up, a colour change or a slow run, the load is lower and some panels will show far less. We agree the route with the production manager so each section is imaged while it runs normally, and the load is recorded with every image so next year’s survey compares like with like.

Heat traps a thermographer has to rule out

  • Process heat: stenters, backing ovens, dye vessels, steam pipework and hot cloth leaving the oven are hot in normal service. Readings are taken at the electrical connection, and panels close to ovens are checked for heat carried in from outside the enclosure.
  • Steam and humidity: dye houses are wet and steamy, which affects what the camera sees across the room. Readings are taken close up, with the cover open where it is safe.
  • Bare metal and reflections: stainless dye vessels, machine guards and shiny busbars reflect heat from nearby sources, so a suspect reading is checked from a second angle before it is reported.

Why load matters

A connection that looks normal at light load can show up clearly at full load. On a London data centre build, our commissioning thermography recorded 16 busbar sections above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Those readings were taken because the system was carrying load when it was imaged.

What the report gives you

Each finding comes with its location by panel and circuit, a thermal image with a matching photo, the measured temperature, the load at the time and the difference in °C from a matching phase or identical unit. Ti inspects and reports; your maintenance team or electrical contractor carries out any work. Reports are on our online portal, usually the same or next working day, in a format insurers and auditors recognise.

Who should do it

Look for a thermographer certified to at least Level 2, with Level 3 oversight, who works within your permit-to-work. Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Your authorised electrician opens and closes panel covers; our thermographer does not touch live equipment.

Frequently asked questions

Does production need to stop?

No. Thermography needs the equipment running. Covers are opened one at a time by your authorised electrician while the mill keeps producing.

How often should a textile or carpet mill be surveyed?

Once a year is a common minimum. Mills running continuously, or with older drive panels, often survey every six months or a few weeks before a planned shutdown.

Can the stenter and backing ovens be surveyed while they run?

Yes. Fan drives, burner control panels and line drives are imaged at working load. The oven casings themselves are hot by design and are not reported as electrical findings.