Short answer: a commercial laundry survey should cover the incoming supply and distribution boards, then the control panels and supplies for washer-extractors, tunnel washers, tumble dryers, flatwork ironers, boilers and compressors. It should be done while the lines are running a normal load, with the heating stages actually on, so connections carry the current they see every shift.
Why laundries need a planned survey
Hospital, hotel and contract laundries run long shifts, often six or seven days a week. The big loads are motors and heaters that start, stop and cycle all day, and much of the plant sits in warm, damp, linty rooms. Electrical connections in that kind of duty can change between visits, and the panels are often next to the machines rather than in a clean switch room.
A thermographic survey is a non-contact way to check those connections under real working load, without stopping production.
What to include
- Incoming supply and main LV switchboard, plus the sub-boards feeding each line
- Washer-extractors and tunnel washers: drive panels, inverters and motor supplies, imaged through a wash and spin cycle
- Tumble dryers: heater contactors and terminals on electrically heated machines, fan and drum motor supplies, and the control panels on gas-heated ones
- Flatwork ironers and folders: heater circuits, drive panels and feeder supplies
- Boiler house and compressors: burner and pump control panels and compressor starters
- Effluent and water treatment panels, where the site has them
Timing: survey during production
Heater circuits only carry current while the heating stage is on, and motor supplies only while the machine is working. We plan the route with the shift supervisor so each machine is imaged in the part of its cycle that loads it, and the load is recorded with every image. A survey on a quiet day or between batches can make a poor connection look fine.
Heat traps a thermographer has to rule out
- Process heat: dryer casings, ironer rolls, steam lines and boiler surfaces are hot by design. Readings are taken at the electrical connection itself, and compared with matching phases or identical machines.
- Reflections: stainless panels and bare copper reflect heat from nearby machines, so the angle is changed and the reading checked.
- Cycling loads: a heater contactor that has just switched off cools quickly. Images are taken while it is energised.
Where lint or dust build-up is visible inside an open panel, it is noted as an observation on the report alongside the thermal finding.
What the report gives you
Each finding is reported with its location by line, machine and panel, a thermal image and a matching photo, the measured temperature, the load at the time, and the difference in °C from a matching reference. Ti inspects and reports; your maintenance team or contractor carries out any work. Reports are on our online portal, usually the same or next working day.
Frequently asked questions
Do the machines need to stop for the survey?
No. Thermography needs equipment energised and working. Your authorised electrician opens covers one at a time while production carries on.
How often should a laundry be surveyed?
Once a year is a common minimum. Sites running long shifts, or that have had findings before, often survey every six months.
Should the machines themselves be included, or just the boards?
Both. Many connections that carry the heaviest loads are in the machine control panels, not the distribution boards.
Related reading
- Surveying a hotel without disturbing guests
- How we plan annual PPM thermography
- Switchgear thermography
- 7 electrical risks behind downtime
- Data centre electrical thermography
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. The same method we use on live data centre switchgear and busbar applies here: image under real load, record the load, compare like with like.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.