Can an electrical thermography survey be carried out in a hotel without disturbing guests?

Yes. Most of a hotel’s electrical distribution is back of house, in switch rooms, risers, plant rooms and kitchens, and it can be surveyed live under normal load with nothing switched off. Boards in corridors or guest areas are opened briefly by the hotel’s engineer at quiet times. Guests shouldn’t notice the survey is happening.

What a hotel survey covers

A typical route takes in the main LV switchboard, rising mains or riser distribution boards on each floor, kitchen and laundry boards, plant room panels for heating, cooling, ventilation and water, lift controllers, and boards serving pools, spas, conference rooms and back-of-house areas. The survey is non-contact: the thermographer images connections with the covers off, and nothing is isolated, so lighting, lifts, kitchens and guest rooms carry on as normal.

Timing it around guests

Thermography needs equipment carrying a typical load, because a connection with little current through it shows little heat. Hotels help here: kitchens, laundries, HVAC and guest rooms put real load on the system for much of the day. The aim is to image each board when it is working, while keeping visible activity away from guests.

  • Back of house first. Main switch rooms, plant rooms and risers can usually be surveyed at any time without anyone seeing the work.
  • Kitchens during service prep. Kitchen boards carry their heaviest load around service, so they are best imaged then, by agreement with the head chef.
  • Corridor and front-of-house boards at quiet times. The engineer opens each one briefly. Imaging a board takes minutes once it’s open.
  • Conference and event boards when they’re in use. A ballroom board imaged on an empty day shows very little.

Who opens the panels

Covers are removed by the hotel’s own engineer or electrical contractor under the site’s permit arrangements. The thermographer images and records. Planning this in advance, with a board list and a route, keeps the visit short and keeps doors closed when guests are around.

What the report gives the engineering team

Each finding comes with thermal and visual images, the measured temperature, exactly where it was taken, the ambient, and the difference in °C from a like-for-like reference, so the engineer can find the exact connection. Findings are prioritised so any investigation can be planned around occupancy and events. Ti inspects and reports; the hotel’s electricians or contractors investigate and carry out any work.

The same approach works on sites where power can’t be interrupted at all. At commissioning on a London data centre build, our thermography found 16 busbar sections over 80 °C under test load, the highest 103.5 °C at a tap-off unit, all located before handover with nothing switched off.

Frequently asked questions

Does anything need switching off?

No. The survey is carried out live. Only panel covers are removed, by the hotel’s engineer.

Can a hotel group’s sites be surveyed on one programme?

Yes. Multi-site groups often survey each hotel in turn on a planned programme, with reports in the same format so sites can be compared.

Is this the same as the periodic electrical inspection?

No. It complements it. Periodic testing is largely carried out with circuits isolated; thermography shows how connections behave under load.

Related reading

Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITN.

Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page

About the author: Rachael Browning, General Manager, Ti Thermal Imaging.