Can an electrical thermography survey be carried out in a laboratory or pharmaceutical cleanroom?

Yes. Laboratories and pharmaceutical sites can be surveyed live, without stopping production or breaking the clean environment. Most of the electrical distribution sits in plant rooms and service corridors outside the classified areas. Boards inside a cleanroom are surveyed under the site’s own gowning and entry procedures, with the camera cleaned before it goes in.

Where the electrical equipment usually is

On most pharmaceutical and laboratory sites the equipment that matters most is not in the cleanroom at all. It is in the plant rooms and service voids that keep the clean areas running:

  • Main LV switchboards and sub-distribution boards
  • Supplies and control panels for the air handling units that hold room pressures and air changes
  • Chiller, cooling and purified water plant panels
  • UPS and supplies to critical equipment such as freezers, stability chambers and monitoring
  • Motor control panels for process plant and utilities

These can be surveyed in the normal way, live, with covers opened by the site’s authorised electrician under the site’s permit to work. See who opens the panels during a survey.

Working inside classified areas

Where boards or process panels sit inside a cleanroom or a controlled laboratory, the survey follows the site’s rules, not ours. In practice that means:

  • Entry times agreed in advance with production and quality teams, around batches and cleaning
  • The thermographer gowned to the site’s procedure for that grade of room
  • The camera and any kit wiped with the site’s approved cleaning agent before entry, and kept to the minimum
  • Panels opened only when the site says it is a suitable time

The same approach works in high-care food production. See surveying high-care food areas.

Timing and load

A thermal survey only shows what is carrying current at the time. Air handling and cooling usually run around the clock, so they can be surveyed on any day. Process equipment often runs by batch or campaign, so the survey is timed for when it is running, not during a shutdown. The load is recorded with each image, so next year’s survey can be compared fairly. See what load a survey needs.

Traps a good thermographer avoids

  • Stainless steel. Cleanroom panels, enclosures and furniture are often polished stainless steel, which reflects heat from people, lights and equipment. Readings are taken on the connections themselves, not on the enclosure surfaces.
  • Process heat. Autoclaves, ovens, incubators and sterilisers are hot by design. Their supplies are judged against matching connections, not against the equipment they feed.
  • Light load. A panel imaged between batches may show nothing even if a connection is poor. The report records the load so it is clear what was seen.

Measured, located findings

We survey pharmaceutical and life-science manufacturing sites alongside data centres, food production and FM portfolios. The method does not change: measure under real load and locate every reading. On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit, each located and imaged.

Ti inspects and reports. Any finding is investigated and put right by the site’s electrical team or contractor.

Frequently asked questions

Does production need to stop for the survey?

No. The survey is done live, and nothing is switched off. Entry to classified areas is planned around the production schedule.

Should the survey be done during the annual shutdown?

Usually not. During a shutdown much of the equipment carries little or no load, so connections cannot be judged. Survey before the shutdown, then use the shutdown to put findings right.

How often should a pharmaceutical site be surveyed?

Most sites survey at least once a year, and some survey critical utilities more often. The site’s insurer or maintenance strategy may set the interval.