Short answer: at a plastic film extrusion or flexible packaging plant, survey the incoming supply and main switchboards, the extruder drive and heater zone panels, the haul-off, winder and slitter-rewinder drives, the printing, laminating and bag-making lines, and the chillers, compressors and material handling. Image during a settled production run, with barrel and die heat ruled out.
Why a film plant needs a planned survey
A blown or cast film line is a long chain of motors, drives and heaters that has to stay in step. Many plants run around the clock, and a tripped drive or heater panel can mean a stopped line, a purge and scrap film before it is back in specification.
Thermography checks the connections feeding that chain under real working load, with nothing switched off. Anything that stands out goes in the report with its location and measured temperature, so the site can plan any work into the next changeover instead of losing a run to a breakdown.
What to include
- Incoming supply, main LV switchboards and sub-boards for the extrusion hall, converting areas, warehouse and offices
- Extrusion: extruder main drive panels, heater zone control panels (contactors, solid-state relays and thyristor units), die and melt pump panels, gravimetric blender and loader supplies
- Line drives: blown film bubble cooling fans, haul-off, collapsing frame and winder drives, cast film chill roll drives
- Converting: slitter-rewinders, laminators, bag and pouch making machines, and the supplies to flexo or gravure presses
- Services: process chillers and cooling towers, air compressors, regrind granulators, silo and vacuum conveying blowers, forklift charging
Timing: a settled production run
Extruder drives and heater zones draw very different current while a line heats up, starts or changes grade. Once a run has settled, the drives carry their normal load and the heater zones cycle at their working rate. We agree the route with the production manager so each line is imaged while it runs normally, and the load is recorded with every image so next year’s survey compares like with like.
Heat traps a thermographer has to rule out
- Barrel, die and melt heat: extruder barrels, die heads, adaptors and melt pipes run hot by design, and panels mounted close to them pick up heat from outside. Readings are taken at the electrical connection with the cover open where it is safe, and process heat is not reported as an electrical finding.
- Cycling heater loads: heater zone contactors and solid-state relays switch on and off to hold temperature, so a single image can catch a circuit off. Matching zones are compared in °C and a suspect reading is re-imaged across a full cycle.
- Parts that run warm by design: solid-state relay and drive heatsinks, braking resistors and transformers are warm in normal service; they are compared with matching units, not reported on their own temperature.
- Bare metal and reflections: chill rolls, idler rolls, stainless guards and shiny busbars reflect heat from nearby sources, so a suspect reading is checked from a second angle before it is reported.
Corona treaters and static control
Corona treaters run at high voltage and high frequency. The treater station itself is not opened for the survey; its supply and control panel are imaged like any other panel, under the site’s permit and with the site’s authorised electrician. Anything the site’s own risk assessment keeps closed is listed in the report as not imaged, so nobody assumes it was checked.
Why load matters
A connection that looks normal at light load can show up clearly at full load. On a London data centre build, our commissioning thermography recorded 16 busbar sections above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Those readings were taken because the system was carrying load when it was imaged, and the same principle applies to a film line.
What the report gives you
Each finding comes with its location by panel and circuit, a thermal image with a matching photo, the measured temperature, the load at the time and the difference in °C from a matching phase or identical unit. Ti inspects and reports; your maintenance team or electrical contractor carries out any work. Reports are on our online portal, usually the same or next working day, in a format insurers and auditors recognise.
Who should do it
Look for a thermographer certified to at least Level 2, with Level 3 oversight, who works within your permit-to-work. Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Your authorised electrician opens and closes panel covers; our thermographer does not touch live equipment.
Frequently asked questions
Do the extrusion lines need to stop?
No. Thermography needs the equipment running. Covers are opened one at a time by your authorised electrician while the lines keep producing.
How often should a film extrusion plant be surveyed?
Once a year is a common minimum. Plants running continuously, or with older drive and heater panels, often survey every six months or a few weeks before a planned shutdown.
Can the heater zone panels be surveyed while the line is at temperature?
Yes, and that is when they should be. The zones are imaged while they cycle at their working rate, and matching zones are compared so a circuit caught switched off is not mistaken for a healthy one.
Related reading
- What to survey in a plastics injection moulding factory
- Should a factory survey before or during its planned shutdown?
- Compressed air plant in an electrical survey
- How we plan annual PPM thermography
- Switchgear thermography
- 7 electrical risks behind downtime
- Busbar thermography at commissioning
- Data centre electrical thermography
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres, FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.