Short answer: whoever owns and maintains each part of the power chain arranges its thermography. In a powered shell, the landlord usually surveys the intake and the supply it delivers up to the demarcation point; the tenant surveys its own fit-out after that, including UPS, switchboards, busbar and PDUs. Your lease or responsibility matrix decides where that line sits.
Why the split matters
A powered shell or wholesale lease hands a tenant a building with power delivered to it. Everything the tenant then installs is the tenant’s to maintain. That is different from colocation, where the operator owns the shared power chain and customers only own their racks.
The risk is the bit in the middle. If the landlord’s survey stops at its last outgoing way and the tenant’s starts at its first incoming board, the cables and terminations between the two can end up on nobody’s list. Before quoting, we ask both sides for their asset list and where the demarcation is written down, so every connection belongs to someone’s survey.
What the landlord usually covers
- LV intake switchboards and the outgoing ways feeding each tenant
- Landlord-owned generators, ATS and changeover panels, where the lease puts them on the landlord’s side
- Shared mechanical plant supplies and the building’s own distribution: lighting, small power, fire and security panels
These can be surveyed live under the landlord’s permit to work, with the site’s authorised electrician opening covers and our thermographer imaging each connection with the load recorded.
What the tenant usually covers
- The tenant’s incoming boards and main LV switchboards
- UPS input, output and bypass connections
- Busbar runs, joints and tap-off units
- Floor PDUs, remote power panels and, where the tenant wants them, rack PDUs
A fully fitted wholesale lease can move some of these to the landlord. That is why the lease, not the building type, decides the scope.
One programme, two reports
The cleanest approach is one survey week covering both sides, with each party’s report going only to that party. Using the same equipment references at the demarcation point means both reports join up, and the connections either side of the handover point are imaged under the same load on the same day.
If only one side commissions a survey, the report says exactly where it stopped, so the other party can see what is not covered.
Load and timing
A connection only shows its condition when it carries current. In a hall that is still filling, we record the load with every image and say plainly when a reading was taken at low load. A survey at commissioning, before the hall goes live, gives every joint a baseline to compare later surveys against.
On one London data centre build, our commissioning thermography recorded 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Each was reported with its location and matching thermal and visual images. Ti inspects and reports; the owner’s own contractor investigates and carries out any work.
Frequently asked questions
Can a tenant survey the landlord’s intake switchgear?
Only with the landlord’s agreement and permit, because it is the landlord’s equipment. Many tenants ask the landlord for a copy of its latest survey instead.
Who should the thermographer report to?
Whoever commissions the survey. Each party gets its own report for its own equipment.
Does a powered shell need a survey before the tenant moves in?
It is worth doing the landlord’s intake and outgoing ways before the tenant takes power, and the tenant’s fit-out during its own commissioning load testing.
Related reading
- Data centre electrical thermography
- Who arranges access in a colocation data centre?
- Commissioning thermography vs the annual survey
- Busbar thermography at data centre commissioning
- Switchgear thermography for data centres
- Annual PPM thermography for data centres
- 7 electrical risks behind data centre downtime
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · send us your site details
About the author: Rachael Browning is General Manager of Ti Thermal Imaging, which carries out electrical thermography for data centres from commissioning to live operation, as well as FM portfolios and industrial sites across the UK and UAE. Ti’s work has featured on BBC News and ITV.