Short answer: a printing works survey should cover the main switchboard and distribution boards, then each press line’s drive cabinets, inverters and motor supplies, dryer and UV or LED curing power supplies, and finishing and bindery equipment. It should be done during a long production run at normal speed, not during make-ready, so the connections carry their working current.
Why presses need a planned survey
A modern press line pulls a lot of current through a small number of cabinets. Main drives, unwind and rewind stands, dryers and curing units all sit on the same line, and an unplanned stop wastes paper, ink and press time as well as the job slot. Many plants run shifts around the clock to keep presses busy.
Thermography checks the electrical connections feeding that equipment under real load, with no shutdown, so anything that stands out can be planned into the next maintenance window.
What to include
- Incoming supply, main LV switchboard and sub-boards feeding each press hall and the finishing area
- Press drive cabinets: main drive and servo drive supplies, inverters, contactors and terminals
- Dryers: hot-air and infrared dryer heater circuits and fan supplies
- UV and LED curing units: the low-voltage supply side and control cabinets
- Finishing and bindery: folders, cutters, stitchers, laminators and their panels
- Support plant: compressors, vacuum pumps, chillers and extraction panels
Any equipment the manufacturer says must stay closed, or that runs at high voltage inside the unit, is left closed and listed on the report as not imaged.
Timing: production run, not make-ready
During make-ready and wash-up, presses run slowly or stop and start, and dryers may be idling. We agree the route with the press supervisor so each line is imaged part-way through a long run at normal speed, with dryers and curing on. The load is recorded with every image, so next year’s survey compares like with like.
Heat traps a thermographer has to rule out
- Process heat: dryer casings, curing lamp housings and heated rollers are hot by design. Readings are taken at the electrical connection, not the machine body.
- Reflections: polished rollers and bare metal reflect heat from nearby equipment, so the angle is changed and the reading checked.
- Cabinet cooling: drive cabinets often have their own fans or coolers, so doors are opened by your authorised electrician and connections imaged directly.
What the report gives you
Each finding comes with its location by line, cabinet and circuit, a thermal image with a matching photo, the measured temperature, the load at the time and the difference in °C from a matching phase or identical unit. Ti inspects and reports; your maintenance team or the press supplier carries out any work. Reports are on our online portal, usually the same or next working day.
Frequently asked questions
Does the press need to stop?
No. Thermography needs the equipment running. Covers are opened one at a time by your authorised electrician while the job runs.
How often should a printing works be surveyed?
Once a year is a common minimum. Plants running around the clock, or with older drive cabinets, often survey every six months.
Can we survey just the presses?
You can, but the boards feeding them carry the same current, so including them gives the whole picture for little extra time.
Related reading
- How we plan annual PPM thermography
- Switchgear thermography
- 7 electrical risks behind downtime
- Busbar thermography at commissioning
- Data centre electrical thermography
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.