Short answer: the incoming supply and main switchboard, the cooking plant (kettles, ovens, steam and fryer supplies), blast and spiral chillers, the refrigeration plant and chilled store panels, the assembly and depositing lines, tray sealing, metal detection and labelling machines with their MCCs and drives. Survey during a normal production shift, with hygiene and panel-opening rules agreed for each zone first.
What should be in scope
- Incoming supply, main switchboard and the distribution boards for goods-in, low-risk and high-risk production, chilled dispatch and offices.
- Cooking: steam kettle, oven, fryer and cooker supplies and control panels, and the boiler or steam plant that serves them.
- Cook-chill: blast chiller and spiral chiller panels, which run hardest straight after each cooking batch.
- Refrigeration: compressor starters and drives, condenser and evaporator fan panels, and chilled store supplies (see refrigeration plant and cold store panels).
- Assembly and packing: depositors, conveyors, tray sealers, sleevers, metal detectors, checkweighers and labellers, with their MCCs and drives (see MCC and VSD panels on a running line).
- Support plant: compressed air, washdown pumps, wastewater and effluent plant.
Low-risk and high-risk zones
Most ready meal sites split production into a raw or low-risk side and a cooked, high-risk side. Main distribution usually sits outside the high-risk area, so the bulk of the survey can be done without entering it. Where local panels sit inside, the thermographer follows the site’s rules for that zone: changing, hand washing, cleared equipment and the route in (see surveys in high-care food areas). Agree which panels can be opened, when, and by whom, and keep openings out of the cleaning schedule. Anything not opened is listed in the report as not imaged.
Timing: when the plant is working
A poor connection shows by the heat it gives off when current flows through it. On a ready meal site the load moves through the day: cooking plant draws heavily during batches, chillers pull down hard straight after, and packing lines carry their normal current only while product is running. Agree a day when the main lines are in full production, plan the route so cooking and chilling panels are imaged while they are working, and record the load against each image. A site that ramps up for seasonal peaks should survey ahead of that peak, not in a quiet week.
Keeping process heat and cold out of the findings
- Heat by design. Kettle and oven casings, steam lines, heater elements and anti-condensation heaters inside panels are warm on purpose. Readings are taken on the electrical connections only.
- Cycling loads. Heater contactors on ovens and kettles switch on and off. A connection is compared with a matching one on the same panel, imaged while it is carrying current.
- Chilled surroundings. In chilled halls a connection is compared with its neighbours at the same load, not with the room, and the camera is allowed to settle when moving between hot and cold areas.
- Bare metal. Stainless enclosures and bare busbars reflect heat from elsewhere. The thermographer checks the angle and the reflection before recording a figure.
Why load matters
On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. They showed because the system was carrying load when it was imaged. A kettle supply or a spiral chiller drive is no different: image it while it is working.
What the site gets
A report issued the same day that locates every finding by board, panel, circuit and phase, with the measured temperature, the difference in °C from its reference and the load at the time, plus a list of anything not imaged and why. That gives your engineering team and your auditors a clear record. Ti inspects and reports; your engineers or electrical contractor decide on and carry out any work. Surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.
Frequently asked questions
Does production need to stop for the survey?
No. Thermography is non-contact and is done with the plant running. Panels are opened one at a time by the site’s electrician (see who opens the panels).
How often should a ready meal factory be surveyed?
Many food sites survey once a year, with critical plant such as cooking and chilling checked more often where a failure would stop production (see how often a food site should survey). Your insurer may set its own interval.
Can the survey be done on a night shift?
Yes, if that is when the lines are in full production. The best time is whenever the plant is carrying its normal working load.
Related reading
- Industrial bakery ovens and control panels
- Survey before or during a planned shutdown
- Data centre electrical thermography
- Busbar thermography at commissioning
- Switchgear thermography
- Annual PPM electrical thermography
- 7 electrical risks thermography finds