When should a train maintenance depot have its electrical thermography survey?

When the depot is at its busiest, which is usually the night shift: trains are stabled, shore supplies are connected and the workshop is running. The survey covers the intake and LV switchboards, train shore supply points, workshop plant such as wheel lathes and jacking systems, the train wash, pit lighting and depot boards. Traction power is scoped separately with the operator.

A daytime survey, with most of the fleet out in service, sees the depot’s supplies at a fraction of their working load. Connections only show their condition when they carry current, so the survey follows the depot’s own rhythm.

What to include

  • Intake and LV main switchboards, including any generator changeover and power factor correction.
  • Shore supply points and their feeder boards, imaged while trains are connected and drawing power.
  • Workshop plant: wheel lathe, synchronised jacking systems, overhead cranes, and their control panels.
  • Train wash drives and control panels.
  • Pit and road lighting boards, workshop and office distribution boards.
  • Compressed air plant and other depot services (see compressed air plant).
  • Outdoor kiosks and feeder pillars along the stabling roads (see outdoor surveys in UK weather).

Where the scope stops

Overhead line equipment, conductor rail and traction substations belong to a different regime, with their own owners and access rules. So does the rolling stock itself. A depot electrical survey covers the depot’s own low-voltage installation; anything on the traction side is scoped separately with the operator and infrastructure owner, if at all.

Timing: follow the stabling pattern

Ask the depot when most units are stabled and on shore supply, and when the heaviest workshop jobs run. Survey the shore supply feeders and main boards then. Workshop plant that runs in short bursts, like a wheel lathe or jacking system, is imaged during a job, or listed as not imaged under load. The report records what was connected and running at each board, so next year’s survey compares like with like (see comparing results year on year).

Access and safety

Depots run on strict rules for walking near live roads and moving trains. The thermographer works under the depot’s own induction, protection arrangements and escort, and any track-safety competence the operator requires is agreed before the visit. Panels are opened by the depot’s authorised person (see who opens the panels).

What runs warm by design

  • Drive heatsinks and braking resistors in workshop and wash panels.
  • Transformers and heaters inside panels and kiosks, including anti-condensation heaters.
  • Kiosks in direct sun.

The findings that matter are connections and components reading warmer than their matching phase, or a matching shore supply point on similar load.

What the report gives you

Each finding is located by board, circuit and phase, or by road and shore supply point, with a thermal and visual image pair, the measured temperature, where it was taken and the difference in °C from the matching reference. We deliver reports the same day. Ti inspects and reports; the depot’s maintenance team investigates any finding with the equipment isolated.

Why survey under load

On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Different site, same principle: connections only show their condition when they carry current (see busbar thermography at commissioning).

Frequently asked questions

Does depot work need to stop?

No. The survey needs the depot working. Panels are opened one at a time and closed again.

Are shore supply sockets included?

Yes, the fixed supply points and their feeders, imaged while trains are connected. The train-side equipment is not.

How often should a depot be surveyed?

Most operators build it into annual PPM, with an extra survey after a new road, fleet or workshop plant is added (see annual PPM thermography).

Related reading

Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.

Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page

About the author: Rachael Browning, General Manager, Ti Thermal Imaging.