The main switchboard and every MCC that drives the process: aeration blowers and their drives, UV disinfection panels, inlet screens, sludge treatment, dosing and pumping. Image them live while the works is treating normal flow, record the running state and load of each panel, and plan any boards inside hazardous areas with the site before the day.
A treatment works never stops, and much of it runs unmanned. That makes a live survey the practical choice: nothing is shut down, and the equipment is imaged doing its real job.
What to include
- Intake and LV main switchboard, including generator changeover and any power factor correction.
- Aeration blower MCCs and drives. On many wastewater works these are among the heaviest electrical loads on site.
- UV disinfection panels and their supplies, channel by channel.
- Inlet works: screens, grit removal and their control panels.
- Sludge treatment: thickening, dewatering and digester plant panels.
- Pumping and dosing panels across the works, and outdoor kiosks and feeder pillars.
Timing: follow the flow
Load on a works follows the flow coming in. Blowers speed up with demand, pumps switch between duty and standby, and some plant runs in batches. Ask the operator when flow is usually highest and survey the main process panels then. Duty and standby sets are each imaged when running, or the one that isn’t is listed as not imaged. The report records drive speed or current for each panel, so next year’s survey compares like with like (see comparing results year on year).
Hazardous areas
Parts of a wastewater works, particularly around digesters and gas handling, are classified hazardous areas. A standard thermal camera is not certified for use inside them. Most MCCs sit in panel rooms outside the zones, but any board inside a zone is imaged only under the site’s own permit arrangements, or listed as not imaged with the reason. Agree this from the site’s area classification drawings before the visit.
What runs warm by design
- Drive heatsinks, braking resistors and transformers inside panels.
- UV ballasts and lamp supplies. Matching channels are compared with each other, not judged on their own.
- Outdoor kiosks in direct sun (see outdoor surveys in UK weather).
The findings that matter are connections and components reading warmer than their matching phase or a matching unit on similar load.
Unmanned sites
Smaller works are often visited rather than staffed. Agree who meets the thermographer, who opens the panels and how lone working is covered (see who opens the panels). Grouping several works into one route saves travel time.
What the report gives you
Each finding is located by panel, circuit and phase, with a thermal and visual image pair, the measured temperature, where it was taken and the difference in °C from the matching reference. We deliver reports the same day. Ti inspects and reports; the operator’s maintenance team investigates any finding with the equipment isolated.
Why survey under load
On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Different site, same principle: connections only show their condition when they carry current (see busbar thermography at commissioning).
Frequently asked questions
Does any plant need to stop?
No. The survey needs plant running. Panels are opened one at a time by the site’s authorised person.
Can drives and soft starters be surveyed?
Yes, while running. The heatsink is expected to be warm; the incoming and outgoing connections are what get compared.
How often should a works be surveyed?
Most operators build it into annual PPM, alongside other maintenance (see annual PPM thermography).
Related reading
- Power factor correction banks
- Generator and ATS changeover panels
- Data centre electrical thermography
- Switchgear thermography
- 7 electrical risks thermography finds
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page
About the author: Rachael Browning, General Manager, Ti Thermal Imaging.