The best time to find a loose connection in a new data centre is while the load bank is running, not after the first client is live. Ti Thermal Imaging images busbars, switchgear, UPS and PDUs during commissioning load tests at sites across Europe, and your report is ready the same day so repairs can be made inside the test window.
Our ITC Level 3 thermographers travel from the UK. We inspect and report. Your electrical contractor makes the repairs, and we can image them again afterwards.
Book commissioning thermography or call +44 20 3885 7464.
Why image at commissioning
Connections are made under programme pressure, by many hands, across thousands of joints. A joint can pass a visual check and an insulation test and still be poorly made. It only shows its hand when current flows, because the heat from a poor connection rises with the square of the current. A fault that is barely visible at 20% load can be serious at full load.
At commissioning on a London data centre build, our thermography found 16 busbar sections over 80 °C under test load, the highest 103.5 °C at a tap-off unit. All were located and recorded before handover. Read more on when to image busbars at commissioning.
What we image
- Busbar trunking, risers and tap-off units
- LV and HV switchgear and main distribution boards
- UPS, static switches and battery connections
- PDUs and remote power panels
- ATS and generator connections
How it fits your commissioning programme
- During the load bank test. We image at the highest stable load the test allows, and record the load at the time of each image.
- Stand-by. Test dates move. We agree a stand-by period with your commissioning manager so we are on site when the load is on.
- Same-day report. Findings go to your contractor while the test rig is still in place, so repairs and re-test happen in the same window.
- Re-image. Repaired connections are imaged again, so the handover record shows each finding closed.
What the report contains
- A thermal image and a matching photo for every finding
- The asset and exact location: hall, room, panel, circuit
- Measured temperature and the load at the time
- A severity grade and a recommended action
We grade to the temperature-difference criteria set out on our data centre electrical thermography page.
Frequently asked questions
Why do thermography during data centre commissioning?
A poorly made joint can pass a visual check and an insulation test, and only show heat once current flows. Imaging during load bank testing finds those joints while your contractor can still fix them before handover.
When in commissioning should thermography be done?
During load bank or integrated systems testing, when current is flowing through the power chain, at the highest stable load you can give us.
Does the test need to be at full load?
No, but higher is better. Heat from a poor connection rises with the square of the current, so a fault barely visible at 20% load can be serious at full load. We record the load at the time of every image so findings can be read in context.
What equipment do you image at commissioning?
Busbar trunking and tap-off units, LV and HV switchgear, main distribution boards, UPS and static switches, battery connections, PDUs, remote power panels, ATS and generator connections.
Does it need a shutdown?
No. It is non-contact and uses energised equipment under load. Your electrician opens panels under your permit to work, and our thermographer never touches live equipment.
How quickly do we get the report?
The same day, so repairs and a re-check can happen inside the same test window.
Do you carry out the repairs?
No. We inspect and report. Repairs are for your electrical contractor, and we can image the repaired connections again so the handover record shows each finding closed.
What if the test date moves?
Dates often do. We agree a stand-by period with your commissioning manager so we are on site when the load is on.