Who should own each finding in a data centre thermography report?

Short answer: each finding should have one named owner. In a data centre that is usually the critical facilities team, which then hands the work to whoever looks after that piece of equipment: the UPS or switchgear service contractor, the installer if it is still in defects, or the tenant for its own racks. Ti reports; your team assigns.

Why ownership gets lost in a data centre

A data centre power path passes through many hands. The landlord may own the incoming supply, the operator owns the switchgear and UPS, a specialist holds the UPS service contract, the busbar installer is still within defects on a newer hall, and a colocation customer owns the rack PDUs. A thermography report covers all of it in one visit. If it lands as a single PDF in one inbox, findings on someone else’s kit can sit unread until the next survey.

A simple way to split the findings

  • Critical facilities or site engineering team: owns the report as a whole, decides the order of work and keeps the record.
  • UPS, switchgear and generator service contractors: findings on the equipment they maintain, raised as work orders under their contract.
  • Installer or main contractor: findings on newly installed equipment still inside the defects liability period, so the cost stays where it belongs.
  • Colocation customer: findings on customer-owned rack PDUs and cabling, passed on through the operator’s normal customer channel.
  • Landlord or building FM: house supplies, BMS panels and landlord switchgear in a shared or powered-shell building.

What the report needs to make this easy

Ownership only works if each finding can be found and passed on cleanly. For every finding the report should give the hall or room, the panel and the exact component, with an asset reference that matches your own CMMS. It should give the measured temperature, where on the component it was taken, the difference in °C from a matching phase or component, and the load at the time. A thermal and a visual image go with each one. That way a finding can be lifted out and sent as a work order without anyone rewriting it.

Closing the loop

A finding is closed when the item has been put right, or checked and found fine, and then re-imaged under load. The owner records what was done against the finding’s reference. Some sites ask for the re-check soon after the repair; others pick it up at the next scheduled survey. Either way, nothing should drop off the list until it has been imaged again. Ti inspects and reports only, so we have no stake in what the repair turns out to be.

Where it starts

The cleanest split is made at commissioning. On one London data centre build, commissioning thermography found 16 busbar sections above 80°C under test load, the highest 103.5°C at a tap-off. Every one went to the installer with its location and images before handover, while it was still clearly theirs to investigate. That report then became the baseline for the operator’s annual surveys.

Ti’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.

Frequently asked questions

Can the report be split by owner?

Yes. Findings can be grouped by hall, system or asset owner, as long as the scope tells us how you want it laid out before the visit.

Who should a colocation customer’s findings go to?

Through the operator, using its normal customer process. The operator decides what is shared and how.

Does the thermographer tell the contractor what to fix?

No. The report says what was measured and where. Finding the cause and putting it right is the job of whoever maintains that equipment.