Should a data centre have a thermography survey after a mains failure or long generator run?

Short answer: yes, bring the next survey forward. A real mains failure puts the generator side, the transfer switches and the UPS recharge path under load they rarely carry, sometimes for longer than any planned test. If the outage runs long, that is the best chance to image the generator path on load; once mains returns, survey the mains side and UPS.

Why an outage is different from a normal day

Thermography finds poor connections by the heat they give off while current flows through them. On a normal day the standby path carries almost nothing: the generator incomer, the generator-side contacts of each transfer switch and the alternator output terminals sit energised but idle (see generator and ATS changeover panels).

A real mains failure changes that. The sets pick up the whole site load, the transfer switches change over and then change back, and the UPS batteries discharge until the generators take over. When mains returns, the UPS draws recharge current on top of the load it is already carrying for a period. That is the load a marginal connection is most likely to show itself under.

If the site is still on generator

The site team’s priority is the event itself, and nothing should get in the way of that. But if the site expects to stay on generator for some hours, and a thermographer can attend under the site’s own permit and access rules, this is the window to image the generator incomers, the generator-side contacts and the alternator terminals where access is safe. They are carrying real site load, not a load bank. The report records that the images were taken during an outage, how long the sets had been on load, and the current shown on the panel or set.

Once mains has returned

Book a live survey of the parts of the power path that the event worked hardest:

  • Transfer switches and changeover panels: the mains side and common load-side connections. The generator side waits for the next on-load test unless it was imaged during the outage.
  • UPS input, output and bypass connections, and the battery string connections if the site wants them in scope.
  • The LV main switchboard and generator incomer panels (see switchgear thermography).
  • Anything that was switched or re-made during the event, for example a manual changeover or a board where a breaker was reset.

Nothing is switched off for the survey. Covers are opened by the site’s authorised electrician under the site’s safe system of work.

Traps a good thermographer avoids

  • Everything is warmer than usual. Equipment that has just carried heavy or recharge current runs warm across the board. Each reading is judged against matching components under the same load, not against last year’s number on its own, and the time since mains returned is recorded.
  • Engine and exhaust heat. Generator rooms are hot by design. Readings are taken on electrical connections only.
  • Anti-condensation heaters in generator and changeover panels are warm by design and are noted, not reported as findings.
  • Bare and shiny metal reflects heat from elsewhere. Suspect readings are checked from a second angle and any limitation is noted.

Why load matters

On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. They showed because the system was carrying load when it was imaged. A standby path that only carries load during an outage is the same: the outage is when it shows what it is really like.

What the site gets

A report issued the same day that locates every finding by panel, circuit and phase, with the measured temperature, the difference in °C from its reference and the load at the time, plus which side of each transfer switch was imaged. Ti inspects and reports; the site’s maintenance team or electrical contractor decides on and carries out any work (see what happens after a survey finds a hot connection). Surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company.

Frequently asked questions

Does an outage mean something has been damaged?

Not necessarily. Most installations come through an outage without any change. The survey gives you a measured record either way, so you are not guessing.

How soon after the outage should the survey be done?

Once the site is stable and back on mains, as a normal live survey. If you also want the generator side, book it for the next planned on-load test.

Can this survey replace our annual survey?

It can, if it covers the full annual scope under normal load. Otherwise treat it as an extra visit and keep the annual one in place (see how often a live data centre should be surveyed).