Yes. A loading bay has a run of small panels that see heavy daily use and are rarely looked at: dock leveller and vehicle restraint controls, door control panels and the boards that feed them. Most of this kit only draws current when it moves, so the survey should be timed for a busy dock period and the load recorded.
Why the loading bay gets missed
Electrical thermography programmes in warehouses and distribution centres usually start with the main switchroom, the big distribution boards and the automation. The dock is a long line of identical small panels spread along an outside wall, often fed from one or two local boards, and it is easy for a survey route to skip it. Yet every dock door and leveller can cycle many times a shift, and the motors, contactors and terminals inside those panels work hard. If a dock goes down at a busy time, vehicles queue and goods sit on the yard.
What should be included
- The distribution boards or sub-boards feeding the dock run, including the outgoing ways to each door and leveller
- Dock leveller control panels: incoming terminals, isolators, contactors and motor connections that can be safely viewed
- Sectional and high-speed door control panels and their local isolators
- Vehicle restraint and dock light supplies where they share the same panels
- On chilled and frozen docks, the supplies to door and frame heaters, recorded as heaters so their normal warmth is not reported as a fault
Getting a meaningful reading
Thermography finds poor connections by the heat they give off when current flows. A leveller pump or door motor draws current for a few seconds at a time, and its connections cool quickly afterwards, so a quiet dock gives a quiet picture. The survey is best timed for the busiest loading window, with the panels imaged straight after the equipment has been in use. The site’s own staff run the docks as normal; we do not operate doors or levellers. The supply board feeding the dock run carries the combined load and is imaged with the current recorded. Anything that had not been in use before it was imaged is noted in the report, so nobody mistakes an idle panel for a clear one.
What the report gives you
Each panel is listed by dock number, so findings can be traced on a busy site with dozens of identical doors. Each finding carries the measured temperature, where it was taken, the reference it was compared with and the difference in °C, with the load at the time. Ti Thermal Imaging inspects and reports; your electrical or door maintenance contractor investigates and carries out any work.
Why location detail matters
On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. Every one was located and imaged before handover. A dock run needs the same discipline: a finding is only useful if it says which door, which panel and which connection.
Frequently asked questions
Do the doors need to be taken out of service for the survey?
No. Panels are opened one at a time by the site’s authorised person and imaged live, so the rest of the dock keeps working.
Are door heaters on cold store docks a fault if they show warm?
No. Heaters are meant to be warm. They are identified and recorded as heaters, and only their supply connections are assessed.
How often should the loading bay be surveyed?
We include it in the site’s annual electrical thermography survey, alongside the main distribution and automation panels.
Related reading
- Thermography in a 24/7 distribution centre
- Conveyor, sortation and automation panels
- Refrigeration plant and cold store panels
- Outdoor electrical equipment in UK weather
- What load is needed for a survey
- What a thermography survey cannot detect
- Thermography across a multi-site FM portfolio
- Data centre electrical thermography
- Annual PPM electrical thermography
- 7 electrical risks thermography finds
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page
About the author: Rachael Browning, General Manager, Ti Thermal Imaging.