Should static transfer switches be included in a data centre thermography survey?

Yes. A static transfer switch (STS) carries the whole load of the racks or PDUs it feeds, so its terminations, breakers and visible internal connections should be imaged live, with nothing switched. Only the source the STS is using carries current, so the report records which source was active for each image.

Why the STS deserves its own line on the survey list

An STS sits between two independent supplies and a load that has only one input, usually a run of single-corded equipment or a downstream PDU. It is there to keep that load running if one source fails. That also makes it a single point the whole downstream load passes through. A survey that covers the UPS and the switchboards but skips the STS leaves a gap right where dual supplies become one.

Static transfer switches are often in the data hall or a gallery rather than the main switch room, which is why they can drop off a survey route that was planned around the switchgear. See covering the whole power path, intake to rack.

What gets imaged

  • Source 1 and source 2 input cable terminations
  • Output terminations to the PDU or distribution it feeds
  • Input, output and maintenance bypass breakers or isolators
  • Internal busbar and cable connections that can be seen safely with covers opened by the site’s authorised electrician
  • Control supplies and fuses

The site’s electrician opens covers under the site’s permit to work. The thermographer does not touch live equipment, and nothing is transferred or switched for the survey.

Preferred source and alternate source

An STS runs from one source at a time. The terminations on the source it is using carry the load and can be judged properly. The terminations on the other source are energised but carry little or no current, so they look cool whether they are sound or not.

That does not make the survey wrong, as long as the report says so. Each image is labelled with the active source and the load shown on the STS display at the time. If the site carries out a planned transfer for its own maintenance, that is a chance to image the other side under load. We fit around those windows; we never ask for a transfer just for thermography.

Traps a good thermographer avoids

  • Power electronics run warm by design. Thyristor heatsinks and cooling air outlets are warm in normal operation. Readings are compared like for like, phase against phase, not against the heatsinks.
  • Bare and shiny metal. Busbar and lugs reflect heat from elsewhere in the room. Readings are taken on suitable surfaces and any limitation is noted.
  • Light load. In a part-filled hall the STS may be carrying little current. The load is recorded with every reading, so next year’s survey can be compared fairly. See what load a survey needs.

How it fits the rest of the survey

On a typical route the STS is surveyed after the UPS output and before the PDUs and rack PDUs it feeds, so a finding can be traced along the chain. The same visit covers UPS and switchgear and rack PDUs in the live hall.

Measuring under real load is the rule everywhere we work. On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit, each located and imaged before handover.

Ti inspects and reports. Any finding is investigated and put right by the site’s electrical team or contractor.

Frequently asked questions

Does the STS need to be transferred for the survey?

No. Nothing is switched. The source in use is imaged under load and the other source is recorded as lightly loaded at the time.

How often should static transfer switches be surveyed?

With the rest of the critical power chain, usually at least once a year. See how often a live data centre should be surveyed.

Will opening the STS covers affect the IT load?

Opening covers does not change how the STS operates. It is done by the site’s authorised electrician under the site’s own safe system of work.

Related reading

Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.