Time the irrigation pump house to the growing season, when the pumps actually run, and arrange a run with the head greenkeeper on the day. Survey the clubhouse on a busy day, when kitchen, bar and heating are all in use, and buggy charging once the fleet is back on charge. A golf club’s loads peak at different times, so the visit is planned around them.
Why one date rarely fits everything
A poor connection shows by the heat it gives off while current flows through it (see what load a survey needs). On a golf course or leisure estate, the big loads come and go:
- Irrigation pumps run in dry weather, often overnight or early in the morning, and sit idle in winter.
- Buggy charging peaks after the fleet comes in, usually late afternoon into the evening.
- The clubhouse is busiest on competition days, at functions and in the heating season.
- Floodlit driving ranges only carry load with the lights on (see floodlight supplies).
Most clubs handle this with one well-planned visit in the season, timed so the pumps can be run, and a short second visit for anything that was idle.
The irrigation pump house
The pump control panel, the variable speed drives, the incoming supply and any booster sets are the core of this part of the survey. Ask the head greenkeeper to run the pumps under a normal irrigation demand while the thermographer is there, rather than surveying an idle panel. Drive heat sinks and some control components run warm by design; the report compares like with like and says where each reading was taken. Outdoor kiosks and pump houses in direct sun pick up heat from the sun, so early morning, before the sun is on them, gives the cleanest images.
What else should be in scope
- Intake and main switchboard, and sub-mains to the clubhouse, maintenance yard and any outbuildings.
- Clubhouse distribution boards: kitchen, bar cellar cooling, changing room water heating and HVAC.
- Buggy charging supplies and the boards that feed them (see EV charger supplies).
- Maintenance yard: workshop supplies, fuel and wash-down equipment.
- Hotel, spa or pool plant on resort estates, surveyed at their own busy times.
Working around golfers and guests
The camera is silent and nothing is switched off, so play and service carry on. Panels are opened by the club’s electrician or maintenance contractor under the club’s own safe system of work (see who opens the panels). Agree the route, keys for the pump house and yard, and the time of the pump run before the day.
What the club gets
A report that locates every finding by panel, circuit and phase, with the measured temperature, where it was taken, the difference in °C from a matching reference and the load at the time. Ti Thermal Imaging issues it the same day. Ti inspects and reports; the club’s electrical contractor investigates findings with the circuit isolated and carries out the work.
Why the pumps must be running
On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. They showed because the busbar was carrying current. An idle pump panel can’t show you the same thing, however carefully it is imaged.
Frequently asked questions
Can we survey the pump house in winter?
Only if the pumps can be run under real load on the day. An idle panel gives a weak result.
Will it disturb play?
No. The thermographer works in plant rooms, the yard and back-of-house areas.
Does it replace the EICR?
No. Thermography finds heat at connections under load; an EICR tests the installation (see does a thermographic survey replace an EICR?).
Related reading
- The best time of year for a survey
- Multi-site FM portfolios
- Data centre electrical thermography
- Switchgear thermography
- Annual PPM electrical thermography
- 7 electrical risks thermography finds
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page
About the author: Rachael Browning, General Manager, Ti Thermal Imaging.