What should an electrical thermography survey cover at a hot-dip galvanising plant?

It should follow the power from the intake and LV switchboards to the plant that keeps the line moving: zinc kettle heating supplies and burner controls, pre-treatment tank heaters and pumps, the flux dryer, overhead cranes and hoists, fume extraction and scrubbers, compressors and effluent plant. Everything is imaged live on a working shift, comparing like with like so radiant heat isn’t mistaken for a fault.

Survey on a working shift

A galvanising plant’s electrical load is uneven. The kettle is held at temperature around the clock, but tank heaters cycle, cranes draw current only while they lift and travel, and extraction fans ramp up when work is dipped. Thermography only shows a weak connection while current is flowing through it, so the survey is booked for a normal production shift, and the route is planned so crane panels and heater supplies are imaged while they are working. The report records what was running when each panel was imaged.

What the scope should include

  • Intake and main distribution: transformer LV tails, main incomers and outgoing feeders to the process line, cranes and services.
  • Kettle heating: the supplies and control panels for the zinc kettle, whether it is electrically heated or gas-fired with electrical burner controls, combustion air fans and temperature control panels.
  • Pre-treatment line: supplies to immersion heaters on the degreasing, pickling and flux tanks, plus circulation pumps and their starters.
  • Flux dryer and quench: dryer fan and heater panels, quench tank pumps and controls.
  • Overhead cranes and hoists: crane isolators, panels and the downshop feed, imaged from agreed positions while the cranes are working. Every jig of steel moves through the plant on them.
  • Fume extraction and scrubbers: kettle enclosure extraction fans, filter plant and acid fume scrubber pumps and fans.
  • Compressors, effluent and MCC rooms: compressed air plant, effluent treatment pumps, and starters, VSDs and feeders across the site (see compressed air plant and MCCs and VSDs imaged while running).

The survey covers electrical panels and connections. Kettle wall and zinc temperatures, tank liquor temperatures, crane mechanical inspection and gas safety checks are separate jobs and sit outside this scope.

Traps a good thermographer avoids

  • Radiant heat from the kettle and dryer. Panels near the kettle can read warm all over. That is not a finding. What matters is the difference in °C between matching connections, phase to phase, on the same circuit.
  • Heaters that cycle. A tank heater contactor imaged during its off period can look clean. The thermographer waits for the heating cycle and records whether it was on.
  • Reflections. Molten zinc, freshly galvanised steel and bare copper all reflect heat, so the thermographer changes angle to check that a hot spot belongs to the connection and not to something behind the camera.
  • Anti-condensation heaters. Panel heaters warm the enclosure, not the connection, and are not reported as findings.

Working in a galvanising plant

The thermographer follows the site induction and PPE rules, keeps to the exclusion zones around the kettle and dipping area, and stays clear of crane routes while loads are moving. Panels are opened by the site’s electrician under the site’s own permit system (see who opens the panels). Production carries on as normal.

What the report gives you

A same-day report that locates each finding by panel, circuit and phase, with a thermal and visual image pair, the measured temperature, where it was taken, the difference in °C from the matching reference and the running state at the time. Areas that could not be imaged safely are listed. Ti inspects and reports. The site’s electrical team or contractor investigates any finding with the equipment isolated.

Why load matters

Load is what makes a weak connection show. On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. In a galvanising plant that means imaging cranes while they lift and heaters while they heat, not on a quiet changeover.

Frequently asked questions

Does the line have to stop for the survey?

No. Thermography images energised equipment on load, so the survey is carried out during a normal shift with work being dipped.

How often should a galvanising plant be surveyed?

Most plants survey once a year, and again after major changes such as a new kettle, a heating system change or new crane equipment.

Can you image the cranes?

Yes, where the site can give safe access. Crane isolators and the downshop feed are imaged from agreed positions while the crane is working, and any panel that can’t be reached safely is listed as not imaged.

Related reading

Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.

Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page

About the author: Rachael Browning, General Manager, Ti Thermal Imaging.