It should follow the power from the LV switchboards through the whole process: beet or raw sugar intake and conveyors, juice and syrup pumps, evaporator and vacuum pan controls, the centrifuge drives, dryers and coolers, silo and bagging lines, and the boiler house supplies. It is all imaged live during the processing campaign, comparing like with like so process heat and steam are not mistaken for faults.
Survey during the campaign
A beet sugar factory works hardest during the campaign, when it runs around the clock, and many refineries run continuously for long periods. That is when the drives, pumps and centrifuges carry their working current, and thermography only shows a weak connection while current is flowing through it. The survey is booked during normal processing, not the off-season shutdown, and the report records what was running when each panel was imaged.
What the scope should include
- LV distribution: main LV switchboards and outgoing feeders to process areas, the boiler house, water treatment and site services.
- Intake and handling: beet reception, washing and conveyor drives, or raw sugar intake conveyors and elevators.
- Process pumps and drives: MCCs and VSDs for juice, syrup and molasses pumps, diffuser and press drives, and agitators (see MCCs and VSDs imaged while running).
- Evaporators and pans: control panels, vacuum pump starters and condenser water pumps.
- Centrifuges: centrifuge drive panels and their supplies, among the largest cyclic loads on site.
- Drying and storage: dryer and cooler fans, silo conveying, screening and the bagging and packing lines.
- Utilities: boiler house and CHP auxiliaries, cooling towers, and the compressed air plant.
The survey covers electrical panels and connections. Boiler and pressure system inspection, mechanical checks and dust explosion assessments are separate jobs and sit outside this scope.
Traps a good thermographer avoids
- Process heat and steam. Evaporators, pans, dryers and steam pipework are hot by design, and panels near them can read warm all over. That is not a finding. What matters is the difference in °C between matching connections, phase to phase, on the same circuit.
- Cyclic centrifuge loads. Batch centrifuges draw heavy current as they accelerate and much less once spinning or discharging. Their panels are imaged across several cycles so each drive is seen working.
- Reflections. Stainless steel vessels, bare copper and polished cabinets reflect heat, so the thermographer changes angle to confirm a hot spot belongs to the connection.
- Dust and condensation. Sugar dust and moisture on enclosures change how surfaces read, so readings are taken from the connections themselves with the panel open.
- Anti-condensation heaters. Panel heaters warm the enclosure, not the connection, and are not reported as findings.
Working on a food site
The thermographer follows the site induction, hygiene and PPE rules, including any dust zone controls, and keeps to agreed routes around process areas. Panels are opened by the site’s electrician under the site’s own permit system (see who opens the panels). Processing carries on as normal.
What the report gives you
A same-day report that locates each finding by panel, circuit and phase, with a thermal and visual image pair, the measured temperature, where it was taken, the difference in °C from the matching reference and the running state at the time. Areas that could not be imaged safely are listed. Ti inspects and reports. The site’s electrical team or contractor investigates any finding with the equipment isolated.
Why load matters
Load is what makes a weak connection show. On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. In a sugar factory that means surveying during the campaign, with the centrifuges and pumps working.
Frequently asked questions
Does processing have to stop for the survey?
No. Thermography images energised equipment on load, so the survey is done while the factory is processing. The off-season shutdown is the worst time because most drives are not running.
How often should a sugar site be surveyed?
Most sites survey once a year during processing, and again after major changes such as new centrifuges, drives or a switchboard replacement.
Can the findings feed into the shutdown plan?
Yes. A survey during the campaign gives the engineering team a list of findings by panel and circuit to investigate when the plant is isolated in the off-season.
Related reading
- Data centre electrical thermography
- Busbar thermography at commissioning
- Switchgear thermography
- Annual PPM electrical thermography
- 7 electrical risks thermography finds
Ti Thermal Imaging’s surveys are carried out by ITC Level 3 thermographers, and Ti is a Level 3 certified company. Our work has featured on BBC News and ITV.
Talk to us: +44 20 3885 7464 · sales@thermalimaging.co.uk · contact page
About the author: Rachael Browning, General Manager, Ti Thermal Imaging.