What should an electrical thermography survey cover at a contract packer or co-packing site?

It should cover the main LV boards and distribution, then every packing line running that week: filling, wrapping and flow-wrap panels, shrink tunnels and heat sealers, labellers, checkweighers, case packers, palletisers and stretch wrappers. Add compressors, chill and ambient store plant and forklift charging. Image everything live on a busy run, and record which line and product was running.

Why a co-packing site is different

A contract packer runs other people’s products on lines that change with each contract. Machines get moved, new lines are added for a launch, and temporary supplies go in to meet a start date. The electrical layout this year is often not the one on last year’s drawings. So the survey starts with a walk-through of what is actually installed and running now, and the report is organised by line as it stands on the day, not by an old schedule.

Survey on a busy run, not a changeover day

Thermography only shows a weak connection while current is flowing through it. Packing lines stop and start for changeovers, cleans and short runs, so the survey is booked for a week with full order volumes, and the route follows the lines that are running. Heat-seal bars, shrink tunnels and heaters cycle on and off, so the thermographer images their supplies while they are switched on and notes the running state against every panel.

What the scope should include

  • Intake and main LV switchboard: incomers, main busbars and outgoing feeders to each hall.
  • Distribution boards and line feeds: including any temporary or recently added supplies put in for a new contract.
  • Packing line panels: fillers, flow-wrappers, tray sealers, labellers, checkweighers, metal detectors and case packers.
  • Heat-sealing and shrink equipment: shrink tunnel and heat-seal supplies and their contactors, imaged while heating.
  • End of line: palletisers, stretch wrappers and conveyor drives.
  • Services: compressed air plant (see compressed air plant), chill and ambient store refrigeration panels, and forklift charging boards.
  • MCCs and drives: starters and VSDs across the site (see MCCs and VSDs imaged while running).

The survey covers electrical panels and connections. Seal quality, product temperatures and mechanical checks on motors and bearings are separate measurements and sit outside this scope.

Traps a good thermographer avoids

  • Heater and seal-bar heat. Shrink tunnels and sealers are meant to be hot. What matters is the connection compared with its matching phases on the same circuit, given as a difference in °C.
  • Cycling loads. A heater contactor imaged during its off period can look clean. The thermographer waits for the on cycle and records it.
  • Reflections. Stainless steel guards and bare copper reflect heat, so the angle is changed to check a hot spot belongs to the connection.
  • Anti-condensation heaters. Panels in chill areas often have them. They warm the enclosure, not the connection, and are not reported as findings.

Working around production and hygiene rules

The thermographer follows the site’s hygiene, PPE and foreign-body rules for each area, and works with the site’s electrician, who opens panels under the site’s own permit system (see who opens the panels). The route is planned around changeovers and cleans so the lines keep running.

What the report gives you

A same-day report organised by line, locating each finding by panel, circuit and phase, with a thermal and visual image pair, the measured temperature, where it was taken, the difference in °C from the matching reference and the running state at the time. Areas that were not running or could not be opened are listed. If a brand customer asks to see your maintenance records, a dated report is one record you can show. Ti inspects and reports; the site’s electrical team or contractor investigates any finding with the equipment isolated.

Why load matters

Load is what makes a weak connection show. On a London data centre build, commissioning thermography by our team found 16 busbar sections reading above 80 °C under test load, the highest 103.5 °C at a tap-off unit. On a packing site the heaviest load is a full run with every line going, which is why the survey is timed around it.

Frequently asked questions

Do the lines have to stop for the survey?

No. Thermography images energised equipment on load, so the survey runs during normal production, ideally in a high-volume week.

How often should a contract packer be surveyed?

Most sites survey once a year, and again after a new line, a major machine move or new supplies for a contract.

What about lines that aren’t running on the day?

They are listed in the report as not on load, so you can see what was covered and book a short follow-up visit when they are running.